 +====== AN016 - Battery replacement procedure ======
 +
 +Before replacing the battery we recommend that you verify that the battery is new:
 +  * charge (use the tester);
 +  * compatibility.
 +
 +For greater security and data protection, make a copy of the data in RAM with the Project procedure > Backup or with the Project procedure > Savedata with the Qview software.
 +
 +__**The battery replacement must be provided with the equipment turned on.**__
 +
 +Replacement descriptions:
 +
 +|Fig.1 Remove the battery cover\\ with flat screwdriver\\ to pry the tabs|
 +|{{:strumenti:qmove:an016:1.png?nolink&250}}|
 +
 +|Fig.2 Replace the battery make sure of\\ respect the polarity|
 +|{{:strumenti:qmove:an016:2.png?nolink&250}}|
 +
 +|Fig.3 Put back the cover battery|
 +|{{:strumenti:qmove:an016:3.png?nolink&250}}|
 +
 +|Fig.4 Turn off and than turn on the instrument|
 +|{{:strumenti:qmove:an016:4.png?nolink&250}}|
 +
 +|Fig.5 If the procedure is correct\\ BATT led stay OFF [(Only for CPU D and E. For CPU B and C, the BATT led can be reset with the Reset allarm battery.)]|
 +|{{:strumenti:qmove:an016:1.png?nolink&250}}|
 +~~REFNOTES~~
 +
 +If after replacing the battery the BATT stays on or flashes you should contact the constructor of the machine.\\
 +If the BATT led turn OFF, but the ERR led flash for Error Checksum, you should restore the data save with the Project procedure > Restore or Project > Recalldata from Qview.\\
 +If you ran a Project > Backup is possible to run the Restore even without the PC.\\
 +If after the installation or battery replacement, HALT led flash, set the data, the time and reset the “Internal Error".\\
 +(Note: if the command does not work, turn off the instrument, turn on the instrument and repeat the procedure)