+ | ====== AN016 - Battery replacement procedure ====== | ||
+ | |||
+ | Before replacing the battery we recommend that you verify that the battery is new: | ||
+ | * charge (use the tester); | ||
+ | * compatibility. | ||
+ | |||
+ | For greater security and data protection, make a copy of the data in RAM with the Project procedure > Backup or with the Project procedure > Savedata with the Qview software. | ||
+ | |||
+ | __**The battery replacement must be provided with the equipment turned on.**__ | ||
+ | |||
+ | Replacement descriptions: | ||
+ | |||
+ | |Fig.1 Remove the battery cover\\ with flat screwdriver\\ to pry the tabs| | ||
+ | |{{: | ||
+ | |||
+ | |Fig.2 Replace the battery make sure of\\ respect the polarity| | ||
+ | |{{: | ||
+ | |||
+ | |Fig.3 Put back the cover battery| | ||
+ | |{{: | ||
+ | |||
+ | |Fig.4 Turn off and than turn on the instrument| | ||
+ | |{{: | ||
+ | |||
+ | |Fig.5 If the procedure is correct\\ BATT led stay OFF [(Only for CPU D and E. For CPU B and C, the BATT led can be reset with the Reset allarm battery.)]| | ||
+ | |{{: | ||
+ | ~~REFNOTES~~ | ||
+ | |||
+ | If after replacing the battery the BATT stays on or flashes you should contact the constructor of the machine.\\ | ||
+ | If the BATT led turn OFF, but the ERR led flash for Error Checksum, you should restore the data save with the Project procedure > Restore or Project > Recalldata from Qview.\\ | ||
+ | If you ran a Project > Backup is possible to run the Restore even without the PC.\\ | ||
+ | If after the installation or battery replacement, | ||
+ | (Note: if the command does not work, turn off the instrument, turn on the instrument and repeat the procedure) | ||