+ | ====== AN021 - Connector wiring ====== | ||
+ | ====== - Types of connectors ====== | ||
+ | |||
+ | ^ ^Family^Wire section\\ without caps^Wire section\\ with caps^Contact\\ features^ | ||
+ | | {{connettori: | ||
+ | | {{connettori: | ||
+ | | {{connettori: | ||
+ | | {{connettori: | ||
+ | | {{connettori: | ||
+ | | {{connettori: | ||
+ | | {{connettori: | ||
+ | |||
+ | < | ||
+ | |||
+ | ===== - BLZF 3.50 ===== | ||
+ | |||
+ | ^ Connectable conductors | ||
+ | | Clamping Range, Sizing link, min. | 0,13 mm< | ||
+ | | AWG Cable Connection Section, min. | AWG 28 | AWG Cable Connection Section, max | AWG 16 | | ||
+ | | Outer insulation diameter, max. | 1,5 mm< | ||
+ | | hard, max. H05(07) V-U | 1,5 mm< | ||
+ | | flexible, max. H05(07) V-K | 1,5 mm< | ||
+ | | with terminal in accordance with DIN 46 228/1, max. | 1,5 mm< | ||
+ | | with AEH terminal with collar DIN 46 228/4, max. | 1 mm< | ||
+ | |||
+ | ==== - Further notes ==== | ||
+ | * Max Outer diameter of the conductor: 2,9 mm | ||
+ | * Terminals without insulating collar according to DIN 46228/1 | ||
+ | * Terminals with insulating collar DIN 46228/4 | ||
+ | * For crimping the terminals we recommend the form A of crimping of clamp PZ 1,5 (cod. art. 9005990000) or, For conductors with larger sections, the PZ 6/5 (cod. art. 9011460000). | ||
+ | |||
+ | < | ||
+ | | ||
+ | ===== - B2L 3.50 ===== | ||
+ | |||
+ | ^Connectable conductors^^^^ | ||
+ | |Clamping Range, Sizing link, min.|0,08 mm< | ||
+ | |AWG Cable Connection Section, min.|AWG 28|AWG Cable Connection Section, max.|AWG 18| | ||
+ | |hard, min. H05(07) V-U|0,2 mm< | ||
+ | |flexible, min. H05(07) V-K|0,2 mm< | ||
+ | |with terminal in accordance with DIN 46 228/1, min.|0,13 mm< | ||
+ | |with AEH terminal with collar DIN 46 228/4, min.|0,13 mm< | ||
+ | ==== - Further notes ==== | ||
+ | * Terminals with insulating collar DIN 46228/4 | ||
+ | * Terminals without insulating collar according to DIN 46228/1 | ||
+ | * For crimping the terminals we recommend the form A of crimping of clamp PZ 1,5 (cod. art. 9005990000) or, For conductors with larger sections, the PZ 6/5 (cod. art. 9011460000). | ||
+ | |||
+ | < | ||
+ | |||
+ | ===== - B2CF 3.50 ===== | ||
+ | |||
+ | ^Connectable conductors^^^^ | ||
+ | |Clamping Range, Sizing link, min.|0,14 mm< | ||
+ | |hard, min. H05(07) V-U|0,14 mm< | ||
+ | |flexible, min. H05(07) V-K|0,14 mm< | ||
+ | |with terminal in accordance with DIN 46 228/1, min.|0,14 mm< | ||
+ | |with AEH terminal with collar DIN 46 228/4, min.|0,14 mm< | ||
+ | |||
+ | ==== - Further notes ==== | ||
+ | * Max diameter of conductor 2,6 mm Terminal with insulating collar in accordance with DIN 46228/4 or in the Weidmüller color code | ||
+ | * tube 1,00 mm² [H1.0/18D] lungh. terminal 12 mm, stripping length 15 mm | ||
+ | * tube 0,75 mm² [H0.75/18D] lungh. terminal 12 mm, stripping length 14 mm | ||
+ | * tube 0,50 mm² [H0.5/16D] lungh. terminal 10 mm, stripping length 12 mm | ||
+ | * tube 0,34 mm² [H0.34/12] lungh. terminal 8 mm, stripping length 10 mm | ||
+ | * tube 0,25 mm² [H0.25/12] lungh. terminal 8 mm, stripping length 10 mm | ||
+ | * tube 0,14 mm² [H0.14/12] lungh. terminal 8 mm, stripping length 10 mm Terminal without insulating collar in accordance with DIN 46228/1 | ||
+ | * tube 1,50 mm² [H1.5/10] lungh. terminal 10 mm, stripping length 10 mm Terminal with insulating collar in accordance with DIN 46228/4 and 2 connected cables | ||
+ | * tube 2 x 0,20 mm² [H0.5/16] lungh. terminal 10 mm, stripping length 12 mm | ||
+ | * tube 2 x 0.34 mm² [H1.0/18] lungh. terminal 12 mm, stripping length 15 mm | ||
+ | |||
+ | < | ||
+ | | ||
+ | ===== - BLF 5.00 ===== | ||
+ | |||
+ | ^ Connectable conductors | ||
+ | | Clamping Range, Sizing link, min. | 0,13 mm< | ||
+ | | AWG Cable Connection Section, min. | AWG 26 | AWG Cable Connection Section, max | AWG 12 | | ||
+ | | hard, min. H05(07) V-U | 0,2 mm< | ||
+ | |flexible, min. H05(07) V-K|0,2 mm< | ||
+ | | with terminal in accordance with DIN 46 228/1, min. | 0,2 mm< | ||
+ | | with AEH terminal with collar DIN 46 228/4, min. | 0,2 mm< | ||
+ | | Caliber in accordance with EN 60999 a x b; Ø | 2,8 mm x 2,0 mm | | | | ||
+ | |||
+ | ==== - Further notes ==== | ||
+ | |||
+ | * Wire and plunger without insulating collar in accordance with DIN 46228/1 | ||
+ | * Wire and plunger with insulating collar in accordance with DIN 46228/4 | ||
+ | |||
+ | < | ||
+ | Terminal 10 mm, stripping length 12 mm | ||
+ | ===== - MSTB 2.5 ===== | ||
+ | == Connectable conductors == | ||
+ | |||
+ | |Rigid conductor section min.|0,2 mm< | ||
+ | |Rigid conductor section max.|2,5 mm< | ||
+ | |Flexible conductor section min.|0,2 mm< | ||
+ | |Flexible conductor section max.|2,5 mm< | ||
+ | |Flexible conductor section with cable lug without plastic collar min.|0,25 mm< | ||
+ | |Flexible conductor section with cable lug without plastic collar max.|2,5 mm< | ||
+ | |Flexible conductor section with cable lug with plastic collar min.|0,25 mm< | ||
+ | |Flexible conductor section with cable lug with plastic collar max.|2,5 mm< | ||
+ | |Conductor cross section AWG min.|24| | ||
+ | |Conductor cross section AWG min.|12| | ||
+ | |2 wires same diameter, hard min.|0,2 mm< | ||
+ | |2 wires same diameter, hard max.|1 mm< | ||
+ | |2 wires same diameter, flexible min.|0,2 mm< | ||
+ | |2 wires same diameter, flexible max.|1,5 mm< | ||
+ | |2 conductors with same diameter, flexible with AEH without plastic collar min.|0,25 mm< | ||
+ | |2 conductors with same diameter, flexible with AEH without plastic collar max.|1 mm< | ||
+ | |2 conductors with same diameter, flexible with TWIN-AEH with plastic collar min.|0,5 mm< | ||
+ | |2 conductors with same diameter, flexible with TWIN-AEH with plastic collar max.|1,5 mm< | ||
+ | |AWG according with UL/CUL min.|30| | ||
+ | |AWG according with UL/CUL max.|12| | ||
+ | |||
+ | |||
+ | |||
+ | ^:info:^For most safer wiring, we recommend the use of Caps^ | ||
+ | |||
+ | < | ||
+ | |||
+ | ====== - Tools ====== | ||
+ | ===== - Caps ===== | ||
+ | ^Wire section^Plunger section^Brand^Model^ | ||
+ | |0,1÷0,3 mm< | ||
+ | |0,3÷0,5 mm< | ||
+ | |::: | ||
+ | |1 mm< | ||
+ | |::: | ||
+ | |||
+ | ===== - Caps crimping Pliers ===== | ||
+ | |||
+ | {{varie: | ||
+ | |||
+ | Model: “Cembre ND#4 cod. 2590086” | ||
+ | |||
+ | ===== - Screwdriver ===== | ||
+ | ==== - Screwdriver for self-locking spring terminals: ==== | ||
+ | |||
+ | {{varie: | ||
+ | |||
+ | Flat blade Screwdriver according to DIN 5264-A. | ||
+ | |||
+ | A = 0,6mm\\ | ||
+ | B = 2,5mm max\\ | ||
+ | C = 7 mm min | ||
+ | |||
+ | ==== - Screwdriver for screw terminals ==== | ||
+ | |||
+ | {{varie: | ||
+ | |||
+ | Flat blade Screwdriver According to DIN 5264. | ||
+ | Tightening torque: 0,4 ÷ 0,5 Nm. | ||
+ | |||
+ | A = 0,6mm\\ | ||
+ | B = 3,5mm | ||
+ | |||
+ | < | ||
+ | |||
+ | ====== - Procedures ====== | ||
+ | ===== - BLZF, B2L, BLZF e BLF ===== | ||
+ | |||
+ | |{{varie: | ||
+ | |{{varie: | ||
+ | |{{varie: | ||
+ | |{{varie: | ||
+ | |||
+ | |||
+ | < | ||
+ | |||
+ | ===== - B2CF ===== | ||
+ | |||
+ | | {{: | ||
+ | | {{: | ||
+ | | {{: | ||
+ | |||
+ | ^: |