Line 1: Line 1:
 +|Connection type|  Potentiometric 1KΩ÷20KΩ  |
 +|Resolution|  12bit/16bit[(It depend on the [[#Hardware versions]])]  |
 +|Reference voltage output|  2,5Vdc  |
 +|Max output current from reference|  10mA  |
 +|Input resistance|  10MΩ  |
 +|Max. Linearity error|  __+__ 0,1% Vfs  |
 +|Max. Offset error|  __+__ 0,1% Vfs  |
 +|S.n.|  71 dB  |
 +|Conversion time|  It depends on the configuration of the analog input.\\ See section [[# Conversion times]] if present [(The sampling time of the device must be equal or higher than the conversion time)]  |
 +|Isolation|  1000 Vrms  |
  
 +~~REFNOTES~~
 +
 +{{schemi:sch_in-potenziometrico_02.png?nolink&400|Potentiometric analog input internal scheme}}