 +/*==== - Ingresso analogico in configurazione PT100 ====*/
  
 +|Sensor type \\ collegabile | PT100 3 wire [(Also connected to 2-wire terminals with jumper)]|
 +|Measure type | Resistance [(Temperature calculated by software)] |
 +|Resolution | 15 bit (32767 corresponds to 250.00 O)|
 +|Input resistance (Rin) | 15 MO |
 +|Measuring current | 1 mA |
 +|Value of damage | 10V |
 +|Accuracy of resistance measurement | ± 0,04% |
 +|Conversion time|  It depends on the configuration of the analog input.\\ See section [[# Conversion times]] if present [(The sampling time of the device must be equal or higher than the conversion time)]  |
 +|Isolation| 1000 Vrms |
 +