Sensor type Thermocouple type J,K,R,S,B,N,T,E 1)
Type of measure Differential voltage
Resolution 16 bit
Measuring range ±156.25 mV
Measure for cold junction compensation Integrated
Input resistance (Rin) 15 MO
Value of damage 30V
Measurement accuracy ± 0,2% (excluding cold junction compensation)
Conversion time It depends on the configuration of the analog input.
See section Conversion times if present 2)
Isolation 1000 Vrms

1) J and K only supported by SW. Contact QEM for the support of the other sensor types.
2) The sampling time of the device must be equal or higher than the conversion time