The electrical features depend on the type of input, configurable via DIP switch.

The conversion times from analog to digital depend on the configuration according to the table:

Analog Input Configuration Conversion time
per channel
Input 1 Input 2
DC1) - 4.6 ms
- DC2) 4.6 ms
DC3) DC4) 9.3 ms
DC5) TC 9.3 ms
DC6) PT100 79.1 ms
TC - 9.3 ms
- TC 9.3 ms
TC DC7) 9.3 ms
TC TC 9.3 ms
TC PT100 83.8 ms
PT100 - 74.5 ms
- PT100 74.5 ms
PT100 DC8) 79.1 ms
PT100 TC 79.1 ms
PT100 PT100 79.1 ms

1), 2), 3), 4), 5), 6), 7), 8) Amperometric, voltmetric or potentiometric type