| + | ====== VC10TCoupleT ====== | ||
| + | |||
| + | The VC10TCoupleT function __Converts a voltage value, expressed in microvolts, to the corresponding temperature value, expressed in tenths of a Celsius degree, connected withe a thermocouple type T__.\\ | ||
| + | Input range : from -5600 μV to 21000 μV\\ | ||
| + | Output range : from -1998 °C< | ||
| + | |||
| + | ===== IMPLEMENTATION ===== | ||
| + | |||
| + | **VC10TCoupleT (mvhot, dgradi_hot, gbError)** | ||
| + | |||
| + | Parameters: | ||
| + | |||
| + | ^IN/ | ||
| + | | IN | GLOBAL | ||
| + | | OUT | GLOBAL | ||
| + | | OUT | GLOBAL | ||
| + | |||
| + | ==== Error ==== | ||
| + | |||
| + | Once invoked the function if there are any errors the error variable having the following values:\\ | ||
| + | 0 - No error\\ | ||
| + | 1 - Value less than the minimum\\ | ||
| + | 2 - Value higher than the maximum\\ | ||
| + | 3 - Value indicating disconnected input | ||
| + | |||
| + | === Example === | ||
| + | |||
| + | <code QCL> | ||
| + | ... | ||
| + | |||
| + | |||
| + | ; Cold-junction reading | ||
| + | |||
| + | card_type = 0 ; using L1TT0 card | ||
| + | |||
| + | IR10CJRead (COLD, card_type, dgradi_cold, | ||
| + | |||
| + | ... | ||
| + | |||
| + | ; Hot-junction reading | ||
| + | |||
| + | card_type = 0 | ||
| + | |||
| + | IR10HJRead (HOT, card_type, mvhot, error) | ||
| + | |||
| + | ... | ||
| + | |||
| + | VC10TCoupleT (mvhot, dgradi_hot, gbError) | ||
| + | |||
| + | ... | ||
| + | |||
| + | temperature = dgradi_cold + dgradi_hot | ||
| + | |||
| + | ... | ||
| + | </ | ||