The P1R11FA10 - 001 application, installed on the Qmove C1-R11-FA10 hardware, it is the Modbus/RTU Slave gateway to the QEM HA548.04 instrument.
Follow we report the main features of the P1R11FA10 - 001 software.
The instrument will need to be supplied with 24Vdc. Isn't necessary the internal fuse.
Nr. 1 MMC card reader for saving/storing from external memory.
Power supply type | 24 Vdc | 24 Vac |
---|---|---|
Valid range | 22 ÷ 27 Vdc | +/-15% |
Max. absorption | 30W | 35VA |
Frequency | 50/60Hz |
1 | AC phase / positive DC terminal | |
2 | Ground | |
3 | AC phase / 0V DC terminal |
1A | A – RS485 MODBUS/RTU Slave | |
2A | B – RS485 MODBUS/RTU Slave | |
3A | 0V - Serial port common. | |
4A | 0V - Serial port common. | |
5A | TX (Transmission RS232) | |
6A | PE - Ground. | |
1B | RX - (Receive “positive” RS422) | |
2B | RXN - (Receive “negative” RS422) | |
3B | TX - (Transmission “positive” RS422) | |
4B | TXN - (Transmission “negative” RS422) | |
5B | RX (Riceive RS232) | |
6B | PE - Ground. |
NB. The DIP SW2 group under the serial port must be set with ONLY THE 5 DIP = ON. |
---|
SW1 | Dip | DIP setting | Function | |||
---|---|---|---|---|---|---|
1 | OFF | OFF | ON | ON | PROG PORT speed selection of transmission | |
2 | OFF | ON | OFF | ON | ||
Baud-rate 38400 | Baud-rate 115200 | Baud-rate 19200 | Baud-rate 57600 |
|||
3 | OFF | OFF | ON | ON | USER PORT speed selection of transmission | |
4 | OFF | ON | OFF | ON | ||
Baud-rate 38400 | Baud-rate 115200 | Baud-rate 19200 | Baud-rate 57600 |
|||
5 | CANbus baud-rate selector. | |||||
6 | OFF | ON | PROG PORT mode of operation selection | |||
PROG PORT can be used by SERCOM and MODBUS device | PROG PORT can't be used by SERCOM and MODBUS device | |||||
7 | CANbus baud-rate selector. | |||||
8 | OFF | ON | Set the USER PORT as PROG PORT1) | |||
Normal PROG PORT | PROG PORT on the USER PORT connector |
CN4 | Terminal | Simbol | Description |
---|---|---|---|
1 | 0V | RS485 serial common | |
2 | B | RS485 B terminal - to connect at the terminal number 2 of the DB9-M connector of the HA548.04 | |
3 | A | Terminale RS485 A - to connect at terminal number 8 of the DB9-M connector of the HA548.04 |
SW4 | Num. Dip | Name Dip | Setting dei DIP | Function |
---|---|---|---|---|
1 | JP3 | ON | Polarizer RS485 | |
2 | JP2 | ON | Termination RS485 | |
3 | JP1 | ON | Polarizer RS485 | |
4 | X1) | none |
You must enable the AUX2 PORT polarizer and termination resistors |
---|