Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Next revision
Previous revision
en:lib:mdl:mdl-h-ceaninp-040 [2015/05/05 08:44] – external edit 127.0.0.1en:lib:mdl:mdl-h-ceaninp-040 [2019/08/29 17:01] (current) – external edit 127.0.0.1
Line 1: Line 1:
 +|Connection type|  Amperometric\\ (0-20 mA)  |
 +|Resolution|  12bit/16bit[(It depends on the [[#Hardware versions]])]  |
 +|Input resistance|  125Ω  |
 +|Value of damage|  25 mA  |
 +|Max. Linearity error|  __+__ 0,1% Vfs  |
 +|Max. Offset error|  __+__ 0,1% Vfs  |
 +|S.n.|  71 dB  |
 +|Conversion time|  It depends on the configuration of the analog input.\\ See section [[# Conversion times]] if present [(The sampling time of the device must be equal or higher than the conversion time)]  |
 +|Isolation|  1000 Vrms  |
 +
 +~~REFNOTES~~
 +
 +{{schemi:sch_in-amperometrico_02.png?nolink&400|Amperometric analog input internal scheme}}