en:lib:mdl:mdl-h-ceaninp-040

This translation is older than the original page and might be outdated. See what has changed.
Connection type Amperometric
(0-20 mA)
Resolution 12bit/16bit1)
Input resistance 125Ω
Value of damage 25 mA
Max. Linearity error + 0,1% Vfs
Max. Offset error + 0,1% Vfs
S.n. 71 dB
Conversion time It depends on the configuration of the analog input.
See section Conversion times if present 2)
Isolation 1000 Vrms

1) It depends on the Hardware versions
2) The sampling time of the device must be equal or higher than the conversion time

Amperometric analog input internal scheme

  • Last modified: 2019/08/29 17:01