+ | ====== DEVICE ANINP2 ====== | ||
+ | |||
+ | |||
+ | ====== - Introduction ====== | ||
+ | |||
+ | * The device manage the reading and processing of an analog input. | ||
+ | * The read data is a word to signed 16-bit which you can add an offset, enter a scaling factor and activate a low-pass RC filter type software. | ||
+ | * Input resolution specifications are listed in the file adapter of the card. | ||
+ | * The outputs can be programmed to perform comparisons on analogue input | ||
+ | |||
+ | {{ : | ||
+ | |||
+ | ===== - Installation ===== | ||
+ | |||
+ | Device declaration in the configuration unit. | ||
+ | In the configuration unit, the BUS section must be declared so that they are | ||
+ | present the hardware resources required for the implementation of the ANINP2 device. Must be at least one analog input with 16-bit resolution.\\ | ||
+ | In the INTDEVICE section of the configuration unit must be to add the following definition: | ||
+ | |||
+ | <code QCL> | ||
+ | ; | ||
+ | ; Devices Declaration | ||
+ | ; | ||
+ | INTDEVICE | ||
+ | ... | ||
+ | <device name> | ||
+ | </ | ||
+ | |||
+ | where: | ||
+ | |<device name> | ||
+ | |ANINP2|Keyword that identifies the device analog input| | ||
+ | |Tcamp|Time sampling device (1÷255 ms)| | ||
+ | |IChn|Address ADC input| | ||
+ | |Type|ID number input type (refer to technical data sheet hardware)| | ||
+ | |Out1|1 Output Address of comparison (to prevent the device uses this resource to put the X.X character)| | ||
+ | |Out2|2 Output Address of comparison (to prevent the device uses this resource to put the X.X character)| | ||
+ | |||
+ | ===== - Example ===== | ||
+ | |||
+ | <code QCL> | ||
+ | ; | ||
+ | ; Device declaration | ||
+ | ; | ||
+ | INTDEVICE | ||
+ | Axis_X | ||
+ | </ | ||
+ | |||
+ | ===== - Operation ===== | ||
+ | |||
+ | When the system is powered, the device checks the correct input type declaration to use defined in configuration (Type) unit.\\ | ||
+ | If the channel diagnostics ends successfully, | ||
+ | // | ||
+ | The conversion of the data output from the (// | ||
+ | is performed using scale factors (// | ||
+ | |||
+ | //**outUm = (scaleA x outbit / scaleB) + scaleC**// | ||
+ | |||
+ | In addition to this updated release based on the sample time of the device, is available the | ||
+ | //outUmF// output, filtered using a programmable charge time (in ms). | ||
+ | |||
+ | ^: | ||
+ | |||
+ | {{: | ||
+ | |||
+ | ==== - Outputs management ==== | ||
+ | |||
+ | The device he can handle analog input mediated comparisons (// | ||
+ | and change the status of the programmable outputs in one shot mode (single activation).\\ | ||
+ | Each output can be handled in the following ways: | ||
+ | |||
+ | |{{: | ||
+ | |{{: | ||
+ | |{{: | ||
+ | |{{: | ||
+ | |{{: | ||
+ | |{{: | ||
+ | |||
+ | ==== - Hysteresis ==== | ||
+ | |||
+ | The device can manage the output comparisons with interests.\\ | ||
+ | Whenever the device varies the State of an output, the input is disabled until the comparison does not deviate from the setpoint hysteresis value.\\ | ||
+ | Specifically the comparison is rearm when the entrance takes on the values listed in the examples following: | ||
+ | |Mode = 1|outUmF = setpoint - hysteresis| | ||
+ | |Mode = 2|outUmF = setpoint - hysteresis| | ||
+ | |Mode = 3|outUmF = setpoint + hysteresis| | ||
+ | |Mode = 4|outUmF = setpoint + hysteresis| | ||
+ | If you are using the 5 snd 6 modes, the output will behave as follows: | ||
+ | | |Activation|Deactivation| | ||
+ | |Mode = 5|outUmF = setpoint|outUmF = setpoint - hysteresis| | ||
+ | |Mode = 6|outUmF = setpoint - hysteresis|outUmF = setpoint| | ||
+ | |||
+ | ===== - Device Error Management ===== | ||
+ | |||
+ | A bug in the device is signaled by the // | ||
+ | When st_error is equal to 1, we find the //errcode// variable for the error type | ||
+ | (see the table) and the // | ||
+ | |||
+ | ^Code^Priority^Description^ | ||
+ | |-|-|-| | ||
+ | |||
+ | If the device goes in error, in order to start the work you must to clear the // | ||
+ | |||
+ | ===== - Warning Device Management ===== | ||
+ | |||
+ | A warning in the camming system is reported by the // | ||
+ | Being caused by a minor event and being guaranteed in this situation, the management of the slave axis, the slave axis continues his work.\\ | ||
+ | When // | ||
+ | (see the table) and in the // | ||
+ | |||
+ | ^Code^Priority^Description^ | ||
+ | |1|0|Command not executed| | ||
+ | |||
+ | To clear the // | ||
+ | |||
+ | ===== - Commands and parameters table ===== | ||
+ | |||
+ | ==== - Symbols used ==== | ||
+ | |||
+ | The **name** of the paramenter, state or command are carry to the left side of the table. | ||
+ | |||
+ | **R**\\ | ||
+ | Indicates if the related parameter or stare is ritentive (upon initialization of the device maintains the previously defined), or is the State that bears upon initialization of the device.\\ | ||
+ | If the device does not need to initialize the ' | ||
+ | R = Ritentive\\ | ||
+ | 0 = At the initialization moment of the device the value is forced to zero.\\ | ||
+ | 1 = At the initialization moment of the device the value is forced to one.\\ | ||
+ | - = At the initialization moment of the device significant value is displayed. | ||
+ | |||
+ | **D**\\ | ||
+ | Indicates the size of the parameter.\\ | ||
+ | F = Flag\\ | ||
+ | B = Byte\\ | ||
+ | W = Word\\ | ||
+ | L = Long\\ | ||
+ | S = Single Float | ||
+ | |||
+ | === - Conditions === | ||
+ | |||
+ | Describes all of the **conditions that is considered correct or because the command is accepted**.\\ | ||
+ | In some cases, limit values are specified for the acceptance of the parameter: If any values outside the limits set, the data will still be accepted; therefore appropriate controls of the application must be provided to ensure proper operation.\\ | ||
+ | To run a command, all the conditions required to be met; otherwise the command does not run. | ||
+ | |||
+ | **A**\\ | ||
+ | Indicates the access mode.\\ | ||
+ | R = Read (read).\\ | ||
+ | W = Write (write).\\ | ||
+ | RW = Read / Write.\\ | ||
+ | |||
+ | ==== - Parameters ==== | ||
+ | |||
+ | ^Name^D^R^A^Conditions^Description^ | ||
+ | |outbit|W|-|R|None|**Output measure in bits**\\ Value read by the input channel offset even.\\ Valid Range: 0 ÷ 32767| | ||
+ | |offset|W|R|RW|None|**Offset compensation**\\ DAC output offset in bit. Defines the value in bits of the correction on the analog input in order to compensate for any drift in the system.\\ Valid Range: -32768 ÷ 32767| | ||
+ | |scaleA|W|R|RW|None|**A Scale**\\A integer parameter scaling formula.\\ Valid Range: -32768 ÷ 32767| | ||
+ | |scaleB|W|R|RW|None|**B Scale**\\B parameter value used in the scaling formula. Must be nonzero.\\ Valid Range: -32768 ÷ 32767| | ||
+ | |scaleC|W|R|RW|None|**C Scale**\\C parameter value used in the scaling formula.\\ Valid Range: -32768 ÷ 32767| | ||
+ | |outUm|L|-|R|None|**Output measure in unity**\\ Derived exit from scaling formula.\\ Valid Range: -32768 ÷ 32767| | ||
+ | |tfilter|W|R|RW|None|**Filter time**\\ Charging time of RC filter. If tfilter < = Tcamp device, the filter is disable. Value expressed in ms.\\ Valid Range: 0 ÷ 32767| | ||
+ | |outUmF|L|-|R|None|**Filtered output in unity of measure**\\ Output in units, filtered.\\ Valid Range: -32768 ÷ 32767| | ||
+ | |hysteresis|L|R|RW|None|**Comparation hysteresis**\\ Hysteresis of comparisons for outputs managing. See the dedicated chapter.\\ Valid Range: -32768 ÷ 32767| | ||
+ | |mode1|B|R|R-W|None|**Function mode 1**\\ Defines the comparison type to be performed on the output shown in the //selout1// parameter.\\ **0** = The output remains in the state it is\\ **1** = Passage activation to the setpoint to the input that increase\\ **2** = Passage deactivation to the setpoint with the count that increases\\ **3** = Passage activation for the setpoint with the input that it decrements\\ **4** = Passage disabling for the setpoint with the input that it decrements\\ **5** = Passage activation for the setpoint with the input that is incremented and passage deactivating with the setpoint to the input that it decrements\\ **6** = Passage disabling for the setpoint with the input that is incremented and passage activation with the setpoint to the input that it decrements\\ Valid Range: 0 ÷ 6.| | ||
+ | |selout1|B|R|R-W|None|**Output selection1**\\ Indicates the first output where the action of the first comparison\\ **0** = Out1\\ **1** = Out2\\ Valid Range: 0 ÷ 1.| | ||
+ | |setpoint1|L|R|R-W|None|**Set point 1**\\ Defines the set point of comparison to be performed on the output shown in the parameter // | ||
+ | |timer1|W|R|R-W|None|**Timer 1**\\ Defines the timer to be running on the output shown in the parameter // | ||
+ | |mode2|B|R|R-W|None|**Function mode 2**\\ Defines the comparison type to be performed on the output shown in the //selout2// parameter.\\ **0** = The output remains in the State where is\\ **1** = Passage activation for the setpoint to the input that you increase\\ **2** = Passage deactivation in step for the setpoint to the input that you increase\\ **3** = Passage activation for the setpoint to the input that it decrements\\ **4** = Passage disabling for the setpoint with the admission that it decrements\\ **5** = Passage activation for the setpoint with the input that is incremented and passage deactivating for the setpoint with the input that it decrements\\ **6** = Passage disabling for the setpoint with the input that is incremented and passage activation for the setpoint with counting that decrements\\ Valid Range: 0 ÷ 6.| | ||
+ | |selout2|B|R|R-W|None|**Output selection2**\\ Indicates the output where the action runs the second comparison\\ **0** = Out1\\ **1** = Out2\\ Valid Range: 0 ÷ 1.| | ||
+ | |setpoint2|L|R|R-W|None|**Set point 2**\\ Defines the set point comparison to be performed on the output shown in the //selout2// parameter.\\ Valid Range: -999999 ÷ 999999.| | ||
+ | |timer2|W|R|R-W|None|**Timer 2**\\ Defines the timer to be running on the output shown in the //selout2// parameter.\\ Valid Range: 0 ÷ 32767.| | ||
+ | |||
+ | |||
+ | ==== - States ==== | ||
+ | |||
+ | ^NAME^D^R^A^Conditions^Description^ | ||
+ | |st_errcfg|F|-|R|None|**Configuration error**\\ Signals that an error was detected in the input configuration.\\ **0** = There was no error.\\ **1** = An error was detected.| | ||
+ | |st_cmp1|F|0|R|None|**Status of first comparation**\\ 1 comparison report.\\ **0** = 1 disable comparison.\\ **1** = 1 active comparison.\\ At the power on by default is set to zero.| | ||
+ | |st_cmp2|F|0|R|None|**Status of second comparation**\\ 2 comparison report.\\ **0** = 2 disable comparison.\\ **1** = 2 active comparison.\\ At the power on by default is set to zero.| | ||
+ | |st_error|F|0|R|None|**Status of device error**\\ Indicates the error status in device.\\ To decode the error you must refer to the errcode and errvalue variables.\\ **0** = Error not present.\\ **1** = Error present.\\ At the power on by default is set to zero.| | ||
+ | |st_warning|F|0|R|None|**Status of device warning**\\ Indicates the warning state in device.\\ To decode the error you must refer to the wrncode and wrnvalue variables.\\ **0** = Warning not present.\\ **1** = Warning present.\\ At the power on by default is set to zero.| | ||
+ | |||
+ | ==== - Commands ==== | ||
+ | |||
+ | Controls were organized by decreasing priority. For example, in the case of contemporary //SETCMP1// and //RESCMP1// controls, is acquired first //SETCMP1// command. | ||
+ | |||
+ | ^Name^Description^Description^ | ||
+ | |SETCMP1|None|**Set of comparation 1**\\ Activates the st_cmp1 status.| | ||
+ | |RESCMP1|None|**Reset of comparation 1**\\ Reset the st_cmp1 status.| | ||
+ | |SETCMP2|None|**Set of comparation 2**\\ Activates the st_cmp2 status.| | ||
+ | |RESCMP2|None|**Reset of comparation 2**\\ Reset the st_cmp2 status.| | ||
+ | |RSERR|None|**Reset error**\\ Reset the st_error status.| | ||
+ | |RSWRN|None|**Reset warning**\\ Reset the st_warning status.| | ||
+ | |||
+ | |||
+ | ===== - Limitations ===== | ||
+ | |||
+ | ==== - Scaling ==== | ||
+ | |||
+ | //ScaleB// must be set to non-zero, otherwise //OutUm// is forced to 0. | ||
+ | |||
+ | ==== - Filter ==== | ||
+ | |||
+ | The charging time of RC element //tfilter// must be set greater than or equal to the time of sampling device (Tcamp), otherwise it disables the filter and the //OutUmF// parameter refreshes that has the same value as //OutUm//. | ||
+ | |||
+ | ==== - Offset ==== | ||
+ | |||
+ | The //offset// parameter is added to the analog input acquired (// | ||
+ | |||
+ | ==== - Configuration ==== | ||
+ | |||
+ | ^:info:^In the case that a single channel is managed by multiple ANINP device with //Type// differents, | ||
+ | |||
+ | A single hardware resource (each input) can be handled by multiple ANINP devices simultaneously, | ||
+ | |||
+ | |||
+ | ===== - Application example ===== | ||
+ | |||
+ | ==== - Configuration Unit ==== | ||
+ | |||
+ | <code QCL> | ||
+ | ; | ||
+ | ; Module Name: Ex_Aninp2.CNF | ||
+ | ; Author: QEM srl Date : 01/05/99 | ||
+ | ; Siystem: QMove1 / QCL3 Library: 1LIB4001 | ||
+ | ; Functionality: | ||
+ | ; | ||
+ | ; [1] - Application example using device ANINP2 | ||
+ | ; | ||
+ | |||
+ | ; | ||
+ | ; Constants Defining | ||
+ | ; | ||
+ | CONST | ||
+ | |||
+ | ; | ||
+ | ; SYSTEM Variable Definition | ||
+ | ; | ||
+ | SYSTEM | ||
+ | slSet1 | ||
+ | slSet2 | ||
+ | |||
+ | ; | ||
+ | ; GLOBAL Variable Definition | ||
+ | ; | ||
+ | GLOBAL | ||
+ | |||
+ | ; | ||
+ | ; TIMER Variable Definition | ||
+ | ; | ||
+ | TIMER | ||
+ | |||
+ | ; | ||
+ | ; DATAGROUP Definition | ||
+ | ; | ||
+ | DATAGROUP | ||
+ | |||
+ | ; | ||
+ | ; Bus Configuration | ||
+ | ; | ||
+ | BUS | ||
+ | | ||
+ | | ||
+ | | ||
+ | | ||
+ | |||
+ | ; | ||
+ | ; INPUT Variable Definition | ||
+ | ; | ||
+ | INPUT | ||
+ | ifAbilComp | ||
+ | |||
+ | ; | ||
+ | ; OUTPUT Variable Definition | ||
+ | ; | ||
+ | OUTPUT | ||
+ | out301 | ||
+ | out302 | ||
+ | |||
+ | ; | ||
+ | ; Internal devices declaration | ||
+ | ; | ||
+ | INTDEVICE | ||
+ | ;Name Type TCamp Counter Type | ||
+ | Axis | ||
+ | |||
+ | END | ||
+ | </ | ||
+ | |||
+ | ==== - ANINP2 management ==== | ||
+ | |||
+ | <code QCL> | ||
+ | ; | ||
+ | ; File name: TASK_00.MOD | ||
+ | ; Project: EX_ANINP2 | ||
+ | ; Description: | ||
+ | ; | ||
+ | |||
+ | ; | ||
+ | ; Initialization work Axis | ||
+ | ; | ||
+ | Axis:offset = 0 ; | ||
+ | |||
+ | ; | ||
+ | ; Scale factor: (scaleA * outbit / scaleB) + scaleC | ||
+ | ; outUm min = (4 * 0 / 8 ) + 3 = 3 | ||
+ | ; outUm max = (4 * 4095 / 8) + 3 = 2050 | ||
+ | ; | ||
+ | Axis: scaleA = 4 ;A scale factor | ||
+ | Axis: scaleB = 8 ;B scale factor | ||
+ | Axis: scaleC = 3 ;C scale factor | ||
+ | Axis: tfilter = 10 ;Capture filter time | ||
+ | Axis: hysteresis = 0 ;Output hysteresis | ||
+ | |||
+ | IF | ||
+ | | ||
+ | ENDIF | ||
+ | IF | ||
+ | | ||
+ | ENDIF | ||
+ | |||
+ | MAIN: | ||
+ | ; | ||
+ | ; Comparisons on the count only if ifAbilComp is active, otherwise the outputs | ||
+ | ; are inactive | ||
+ | ; ----------------------------- used variables -------------------------------- | ||
+ | ; slSet1: Comparison quota for 2.OUT01 output | ||
+ | ; slSet1: Comparison quota for 2.OUT02 output | ||
+ | ; | ||
+ | |||
+ | IF ifAbilComp | ||
+ | IF NOT gfApp01 | ||
+ | Axis: mode1 = 5 ; | ||
+ | Axis: selout1 = 0 ;and disable out1 if posit < setpoint1 | ||
+ | Axis: setpoint1 = slSet1 | ||
+ | Axis: timer1 = 0 | ||
+ | Axis: mode2 = 6 ; | ||
+ | Axis: selout2 = 1 ;and disable out2 if posit < setpoint2 | ||
+ | Axis: setpoint2 = slSet2 | ||
+ | Axis: timer2 = 0 | ||
+ | | ||
+ | | ||
+ | ENDIF | ||
+ | ELSE | ||
+ | IF NOT gfApp02 | ||
+ | | ||
+ | | ||
+ | Axis: selout1 = 0 | ||
+ | Axis: mode2 = 0 | ||
+ | | ||
+ | Axis: selout2 = 1 | ||
+ | | ||
+ | | ||
+ | ENDIF | ||
+ | ENDIF | ||
+ | |||
+ | ; | ||
+ | ; Final operations | ||
+ | ; | ||
+ | WAIT 1 | ||
+ | JUMP MAIN | ||
+ | END | ||
+ | </ | ||
+ | |||