OT21PidReg
O = Digital Output
T = Control functions
The OT21PidReg function implements a generic PID controller. In addition to providing the regulation value, the function operates two digital signals are modulated pulse width to handle positive and negative representation of control output.
IMPLEMENTATION
OT21PidReg ( aswParReg , aswParUsr, gwSetPoint, gwMeasure, gfEnaReg, aglOutReg )
Parametri:
IN/OUT | VARIABLE TYPE | EXAMPLE NAME | DIM | |
---|---|---|---|---|
IN | ARRSYS | aswParReg [1] | W | Sample time PID controller (msec) [0÷32767]. |
IN | ARRSYS | aswParReg [2] | W | Maximum scale limit of process variable (UM) [-32768÷32767] |
IN | ARRSYS | aswParReg [3] | W | Minimum scale limit of process variable (UM) [-32768÷32767] |
IN | ARRSYS | aswParReg [4] | W | Maximum value control output [-32768 ÷32767] |
IN | ARRSYS | aswParReg [5] | W | Minimum value control output [-32768 ÷32767] |
IN | ARRSYS | aswParUsr [1] | W | Proportional gain.(‰ )[0÷9999] |
IN | ARRSYS | aswParUsr [2] | W | Integral time (msec) [0÷9999] |
IN | ARRSYS | aswParUsr [3] | W | Derivative time (msec) [0÷9999] |
IN | ARRSYS | aswParUsr [4] | W | Sample time of the derivative [0÷255] 0=sample time PID controller 1=2*sample time PID controller … … n=(n+1)*sample time PID controller |
IN | ARRSYS | aswParUsr [5] | W | Derived filter time constant (msec.) [0÷9999] |
IN | ARRSYS | aswParUsr [6] | W | Feed Forward (‰) [0÷2000] |
IN | GLOBAL | gwSetPoint | W | Adjustment setpoint (UM) |
IN | GLOBAL | gwMeasure | W | Value of the process variable (UM) |
IN | GLOBAL | gfEnaReg | F | Enabling regulation [0÷1] 0=regulator disabled 1=regulator enabled |
OUT | ARRGBL | aglOutReg[1] | L | PID output log |
OUT | ARRGBL | aglOutReg[2] | L | Proportional output log |
OUT | ARRGBL | aglOutReg[3] | L | Integral output log |
OUT | ARRGBL | aglOutReg[4] | L | Derivative output log |
OUT | ARRGBL | aglOutReg[5] | L | Feedforward output log |
OUT | ARRGBL | aglOutReg[6] | L | Error log |
OUT | ARRGBL | aglOutReg[7] | L | Regulator states: bit 0 = State pwm output for positive adjustment bit 1 = State pwm output for negative regulation bit 2 = positive saturation state bit 3 = negative saturation state bit 4 + executing state regulation |
OUT | ARRGBL | aglOutReg[8] | L | Error code |
Errors
Once call the function, the “Error Code” variable in aglOutReg[8] assumes certain values, the meaning of these values is summarized below:
0: No error
1: Error setting sampling time
2: Error setting lower limit and/or greater of scale
3: Error setting value proportional gain
4: Error setting integral time
5: Error setting derivative time
6: Error setting feed-forward percentage value
7: Error setting minimum and/or maximum value regulator output
8: Error setting sampling time derivative
9: Error setting derived filter time constant
Example
;--------------------------------------------- ; Example ;--------------------------------------------- aswParReg [0]=500 ; Sampling time = 500ms aswParReg [1]=10000 ; full scale over = 10000 aswParReg [2]=0 ; full scale less = 0 aswParReg [3]=500 ; Maximum value output regulator aswParReg [4]=0 ; Minimum value output regulator aswParUsr[1] = 100 ; Proportional gain = 0.1 aswParUsr[2] = 200 ; Integral time = 0.2 sec. gfEnaReg = 1 ;Enable regulation MAIN: gwSetPoint = 800 OT20PidReg ( aswParReg , aswParUsr, gwSetPoint, gwMeasure, gfEnaReg, aslOutReg ) ofOutPow = aslOutReg[7] ANDB &H01 WAIT 1 JUMP MAIN
Definition of controller
A regulator reads an (gwMeasure) input variable, compares with to a reference signal (gwSetPoint) and change the value of the (aslOutReg[7]) output to achieve equality of the variable with the reference.
PID regulator
One of the most popular types of regulator is the PID (Proportional, Integral, Derivative).
Proportional action
This control action establishes a relationship of direct proportionality between the error (aglOutReg[6]) and the value at the regulator output. The gain proportional parameter (aswParUsr [1]) defines the degree of proportional controller; It's expressed in milliseconds for which to set a gain of 0.5 it should enter the value 500.
The rule that establishing the output value (aslOutReg[7]) defines: with unity gain (1000), the control output will be maximum when the error is equal to the difference between “Maximum scale limit” and “Maximum scale limit” that is the result between aswParReg [2] - aswParReg [3].
Azione integrale
L'azione integrale del regolatore PID calcola l'integrale dell'errore su un intervallo di tempo impostabile dall'utente tramite il parametro aswParUsr [2] (espresso in ms). Il segnale di uscita viene aggiornato in modo particolare: ogni volta che l'integratore da un valore in uscita questo è sommato al valore che si trova sul registro, quindi esso continuerà ad incrementarsi o decrementarsi (a seconda del segno dell'errore). Il valore d'uscita è calcolato così: con guadagno proporzionale unitario, il tempo di integrazione (aswParUsr [2]) è il tempo necessario affinché lil registro integrale (aglOutReg[3]) raggiunga il valore del registro proporzionale (aglOutReg[2]). Da quest'ultima affermazione si deduce che l'azione integrale è legata all'azione proporzionale.
Azione derivativa
L'azione derivativa cerca in un certo senso di “anticipare” il comportamento del sistema che si sta controllando. L'uscita prodotta è proporzionale alla variazione del segnale di ingresso. L'entità dell'effetto derivativo è impostabile tramite il parametro tempo derivativo (aswParUsr [3]). Il calcolo dell'azione derivativa si basa sulla seguente convenzione: il tempo derivativo è il tempo necessario affinché, con variazione di errore costante, il registro derivativo (aglOutReg[4]) raggiunga un valore pari al registro proporzionale (aglOutReg[2]). Come per l'azione integrale si evince che anche per l'azione derivativa c'è un legame con l'azione proporzionale. Più alto è il tempo di derivazione dell'errore e più veloce è il sistema nel recupero dell'errore nei transitori. E' evidente comunque che l'azione derivativa non può mai essere utilizzata da sola perché in presenza di errori costanti il suo effetto sarebbe nullo.
Azione feed-forward
In aggiunta al regolatore PID è presente anche l'azione feed-forward: essa genera un'uscita proporzionale al valore di setpoint (come si può dedurre dal nome non sfrutta alcuna retroazione dell'errore). La sua funzione è di ridurre il tempo di risposta del sistema fornendo un'uscita già vicina a quella che il regolatore dovrebbe raggiungere. Il contributo di questa azione è regolabile mediante il parametro feed forward (aswParUsr [6]): questo parametro è espresso come porzione millesimale (quindi per introdurre, ad esempio, 98.5% è necessario impostare il valore 985).
DIFFERENZE RISPETTO ALLE VECCHIE RELEASE
-
(dalla 20 alla 21) Aggiunto uno stato di esecuzione regolazione. ? Evitato un errore ““division by zero” alla prima esecuzione ? Evitato di azzerare l'uscita integrale OUTI se ti=0. Questo serve per poter sospendere l'esecuzione del pid e riprenderla senza che il registro integrale venga alterato.