AN017
Procedure
Switch off the controller power
Insert the MMC card containing the application programs in the controller
Press F1 key (or FUNC on back) and power the controller.
Keep the F1 key (or FUNC on back) pressed until the System Functions screen is opened
The Qmove application does not startup and the “SYSTEM FUNCTIONS” screen will open.
The screen shows function option 01 Reset Error Checksum as shown below, it is also indicated by the L1 led on the back of the controller
(See below for the System Function options and L1-L2-L3-L4 led combinations)
Press F1 key (or FUNC on back) to change function option screens one by one.
Go to the Function Option 05 - Application upload from MMC/SD screen (L1-L3 led's on back)
Press ENTER (or BOOT on back) for 2 seconds to execute the function on display.
A PASSWORD entry box opens - use the number keys to enter 1 2 3 and press ENTER
inserisci immagine della finestra PASSWORD
The function starts and is confirmed by the message “Executing”, showing the percentage progress
The SUCCESSFUL message in green shown on screen
To restart the controller press F1 key (or FUNC on back)
If there is an error the pow stops blinking and the ERR starts blinking. The screen gives a message with the ERROR CODE in red.
See the ERROR CODE table and corresponding led's below |
System Function options
If the “PWD” column has 'Y' the function requires a system password (default: “123”).
System Functions
N.B. To quit System Functions press F1 (or FUNC on back) for at least two seconds.
Error Messagge
When a system error ends with an error, the number of Quando una funzione di sistema termina con errore, il numero di lampeggi del led err led blinks a number of times to indicate the type of error.
System Functions Error Messages
Error/ERR Led blinks | Messagge |
---|---|
1 | Generic error |
2 | Open/Exist/Create file error |
3 | Read file error |
4 | Write file error |
5 | Out of Memory error |
6 | QMos Version error |
7 | Checksum Error |
8 | Symbols checksum No Match |
9 | Configuration / Symbols error |
10 | File format error |
11 | Format error |
12 | Device not present or unformatted |
13 | Application not present error |
14 | Touch calibration failure |
15 | File compression type not support |
16 | Target don't match project ! |
17 | Fw version don't match project ! |
18 | File copy error |
19 | File size error |
20 | Crypt operation error |
21 | Invalid Product Serial Number |
22 | Function is locked |
Il numero di lampeggi indica il tipo di errore avvenuto come riportato nella tabella Messaggi di errore delle Funzioni di sistema.