Reset checksum error procedure on R201A

The purpose of the following document is to integrate the procedure already described in the Hardware Manual of the R201 to pag. 22.

  • Instrument in error CHECKSUM: led PWR fixed, led ERR makes two flashes.

  • Restart the instrument by pressing and holding the FUNC key

  • So you enter in the system functions: led PWR on and led L4 on.

  • Press the BOOT key for 2 seconds.

  • Start the error reset procedure: led PWR flashes.
  • End the error reset procedure and the instrument restarts.
  • NOTE: If, to end the L4 and ERR LED lights up fixed manually restart the instrument.

  • To the end the R201 instrument return in run state

  • If the R201 is in checksum error then in the QC043 will appear the following screen:

  • Press the F2 key on the panel to continue.