en:lib:mdl:mdl-h-cers485-010

This translation is older than the original page and might be outdated. See what has changed.

.

Communication speed4800 baud (only if used with SERCOM and/or MODBUS device),
9600 baud, 19200 baud, 38400 baud, 57600 baud
Communication modeHalf duplex
Operating modeDifferential
Max. number of devices connected on the line32
Max. cable length1200 m
Input impedence> 12 Kohm
Short-circuit current limit35 mA

Internal wiring diagram of RS485

Cable connection diagram of RS485

  • Last modified: 2019/08/29 17:01