:todo:The cabling must be carried out by specialist personnel and fitted with suitable anti-static precautions.
Before handling the controller, disconnect the power and all parts connected to it.
To guarantee compliance with EC regulations, the power supply must have a galvanic isolation of at least 1500Vac.
Power supply 24 Vdc
Voltage range 22 - 27 Vdc
Max. absorption 30W

Connector

CN1 TerminalSymbolDescription
1 L1/+ DC power positive
2 GROUND Gnd-PE (signals)
3 L2/- DC power 0V
:todo:Use an isolated power unit with 24Vdc +/-5% output conform to EN60950-1.
Use two separate power units: one for the control circuit and one for the power circuit
For a single power unit, use two separate lines: one for the control and one for the power
DO NOT use the same lines for the power circuit and the controller