Connettore

@cnn@ Connector Simbol Description Address
1 GAI Analog inputs common
2 VREF Reference voltage 1)
3 AI1_A Analog input 1 @slot@.AI01
4 AI1_B
5 AI1_C
6 AI2_A Analog input 2 @slot@.AI02
7 AI2_B
8 AI2_C

1) For potentiometric inpus

Analog inputs setting

Num.
Dip
Analog input 1 Analog input 2
PT100 Termocouple Pot. 0-10V 0-20mA PT100 Termocouple Pot. 0-10V 0-20mA
@dipb@
dip-8.jpg
1 ON X OFF OFF OFF X X X X X
2 OFF X ON ON ON X X X X X
3 X X X X X ON X OFF OFF OFF
4 X X X X X OFF X ON ON ON
5 ON ON OFF OFF OFF X X X X X
6 OFF OFF ON ON ON X X X X X
7 OFF ON X X X X X X X X
8 X X X X X OFF ON X X X
@dipa@
dip-4.jpg
1 X X OFF OFF ON X X X X X
2 X X OFF ON OFF X X X X X
3 X X X X X X X OFF OFF ON
4 X X X X X X X OFF ON OFF

X = setting not significant
Pot. = potentiometric type input