en:lib:tpl:tpl-h-cnaninp-022

This translation is older than the original page and might be outdated. See what has changed.

Connector

@cnn@ Terminal Simbol Description Address
Potentiometric / 0-10V / 0-20mA Termocouple PT100
1 GAI Analog inputs common - -
2 VREF Reference volatege 1) - -
3 AI1_A Analog input 1 - A 2) @slot@.AI01
4 AI1_B - TC 1 - B
5 AI1_C - TC 1 + C
6 AI2_A Analog input 2 - A 3) @slot@.AI02
7 AI2_B - TC 2 - B
8 AI2_C - TC 2 + C

1) For potentiometric inputs
2), 3) A and B cables connected to the resistance, have the same color.
In the case of 2-wire PT100 you must make a jumper between A and B.

Analog inputs setting

Num.
Dip
Analog input 1 Analog input 2
PT100 Termocouple Pot. 0-10V 0-20mA PT100 Termocouple Pot. 0-10V 0-20mA
@dipb@
dip-8.jpg
1 ON X OFF OFF OFF X X X X X
2 OFF X ON ON ON X1) X X X X
3 X X X X X ON X OFF OFF OFF
4 X2) X X X X OFF X ON ON ON
5 ON ON OFF OFF OFF X X X X X
6 OFF OFF ON ON ON X X X X X
7 OFF ON X X X X X X X X
8 X X X X X OFF ON X X X
@dipa@
dip-4.jpg
1 X X X X X X X OFF OFF ON
2 X X X X X X X OFF ON OFF
3 X X OFF OFF ON X X X X X
4 X X OFF ON OFF X X X X X

X = setting not significant
Pot. = potentiometric type input


1) To set OFF if not use for analog input 1
2) To set OFF if not use for analog input 2
  • Last modified: 2019/08/29 17:01