To activate the internal termination resistance see paragraph Setup Termination resistances
.
| Communication speed | 125, 250, 500, 1000 Kbit/s |
|---|---|
| Max. number of Drivers/Receivers on the line | 100 |
| Max. cable lengths | 500m @ 125Kbit/s, 250m @ 250Kbit/s, 100m @ 500Kbit/s, 25m @ 1000Kbit/s |
| Input impedence | >15Kohm |
| Short-circuit current limit | 45mA |
CAN BUS connection examples.
Caution:
Close DIP's JP1 and JP2 and insert the termination resistances (RL, RH) on the last device of the chain.