Connector
CN2 TerminalRS232RS422RS485Description
1A - - A Terminal A - RS485
2A - - B Terminal B - RS485
3A 0V 0V 0V USER PORT common
4A 0V 0V 0V USER PORT common
5A TX - - Terminal TX - RS232
6A Terra
1B - RX - Terminal RX - RS422
2B - RXN - Terminal RX N - RS422
3B - TX - Terminal TX - RS422
4B - TXN - Terminal TX N - RS422
5B RX - - Terminal RX - RS232
6B Ground
Setup of USER PORT electric standard
SW2 Num.
Dip
Name
DIP
Setting
of DIP
Function
1 JP2 ON X1) X2) Termination RS485
2 JP3 ON X3) X4) Polarization RS485
3 JP1 ON X5) X6)
4 OFF ON OFF Selection of USER PORT electric standard
5 ON OFF OFF
6 OFF OFF ON
RS485 RS422 RS2327)

1), 2), 3), 4), 5), 6) X = setting not significant
7) the USER PORT can be used as PROG PORT with RS232 electric standard, setting ON in DIP-8 of SW1 and OFF in DIP-6 of SW2