C1-R44-Fx BASE

C1-R44


All rights reserved on this manual. No part of this document can be copied or reproduced in any form without prior written authorisation. QEM does not insure or guarantee its contents and explicitly declines all liability related to the guarantee of its suitability for any purpose. The information in this document can be changed without notice. QEM shall not be held liable for any error or omission in this document. QEM® is a registered trademark.

Informations

Documento: MIMC1R44Fx BASE
Description: Installation and maintenance manual
Editor: Riccardo Furlato
Approver Gabriele Bazzi
Link: http://www.qem.eu/doku/doku.php/en:strumenti/qmoveplus/C1R44/mimC1R44fx_base
Language: English
Document release Hardware Release Description Note Date
01 01 New manual / 19/02/2015
02 01 Fixes / 07/04/2015
03 01 Fixes description DIP-SW4 / 01/07/2015
04 01 Fixes the description of the analog input connector CN13 / 24/08/2015
05 01 Added new section “General information of operation” / 13/01/2016
06 01 Fixes the description of the setting of the analogue inputs and related connection examples / 01/02/2015
07 01 New “FE” version and connection between the expansion card “1MG2F” / 16/05/2016
08 01 Fixed the description of connectors CN14-17, for frequency meter inputs / 05/09/2016

The controller has been designed for industral environments in conformity to EC directive 2004/108/CE.

  • EN 61000-6-4: Electromagnetic compatibility - Generic standard on emission for industrial environments
    • EN55011 Class A: Limits and measurement methods
  • EN 61000-6-2: Electromagnetic compatibility - Generic standard on immunity for industrial environments
    • EN 61000-4-2: Electromagnetic compatibility - Electrostatic discharge immunity
    • EN 61000-4-3: Immunity to radiated, radio-frequency electromagnetic field
    • EN 61000-4-4: Electrical fast transients
    • EN 61000-4-5: Surge immunity
    • EN 61000-4-6: Conducted disturbance induced by radio-frequency
  • Moreover the product is conform to the following standards:
    • EN 60529: Housing protection rating IP64
    • EN 60068-2-1: Environmental testing: Cold
    • EN 60068-2-2: Environmental testing: Dry heat
    • EN 60068-2-14: Environmental testing: Change of temperature
    • EN 60068-2-30: Environmental testing: Cyclic damp heat
    • EN 60068-2-6: Environmental testing: Sinusoidal vibration
    • EN 60068-2-27: Environmental testing: Shock vibration
    • EN 60068-2-64: Environmental testing: Random vibration

1. Description

The C1-R44-F is the compact instrument for panel mounting of the Qmove+ range.

:tip:The Ordering Code provides the exact product features.
Make sure that the product characteristics meet your requirements.

  • a - Ordering Code
  • b - Week made: indicates the week and year of manufacture
  • c - Part number: unique code that identifies an ordering code
  • d - Serial number: product serial number, different for individual product
  • e - Hardware release: version of hardware release

Model Features
C1 - R44 - FA - 10
10 = Firmware version (00 = not installed)
F = Technology level
A = Hardware version
R = Rear panel mounting instrument;
4 = Dimensions (251x175mm)
4 = Firmware-hardware correspondence
C1 = “Motion” Qmove family

These are hardware versions currently available:

Hardware versions
A B C E Y
SLOT 2
(Base card)
USER PORT (RS232-422-485) 1 1 1 1 1
AUX PORT (RS485) 1 1 1 1 1
CAN1 PORT 1 1 1 1 1
CAN2 PORT 1) - - - - -
ETHERNET PORT 1 1 1 1 1
USB PORT 1 1 1 1 1
Standard digital inputs 16 16 16 16 16
Rapid digital inputs (can be used as frequency meters) - 2 2 2 2
Analog inputs 16bit selectable(0-10V, 0-20mA, potenziometric, termocouples, PT100) 2 2 2 2 2
Bidirectional counters 200KHz ABZ (24V-PP, 5V-LD) - 2 4 2 4
SSI counter inputs - - - - 2
Protected digital outputs 16 16 16 16 16
Stepper outputs - - - - 2
Analog outputs +/-10V-16bit - 2 4 2 4
CSoftware code of the card to declare as base card 1QM4F
Expansion
card
Standard digital inputs - - - 16 -
Analog inputs 12bit - - - - -
Analog inputs 16bit seleectable (0-10V, 0-20mA, potenziometric, termocouples, PT100) - - - - -
Protected digital outputs - - - 16 -
Relay digital outputs - - - - -
Analog outputs 0-10V-12bit - - - - -
Analog outputs +/-10V-16bit - - - - -
Bidirectional counters 200KHz ABZ (24V-PP, 5V-LD) - - - - -
Software code of the card to declare as expansion card - - - 1MG2F -
VersionDescription
10 Fully programmable with PLC functions
20 Fully programmable with PLC and Motion control functions
30 Fully programmable with PLC, Motion control, Camming and Interpolation functions

For more details about the firmware, consult Devices enabled in the controllers.

The C1-R44-F composed of a “base” card and an “expansion” card.

  • a = Base card
  • b = Expansion card

2. Technical features

Weight (maximum hardware configuration)1.2Kg
Material boxSheet metal
System led8
System keys3
Operating temperature0 ÷ 50°C
Transport and storage temperature-25 ÷ +70 °C
Relative humidity90% condensate free
Altitude0 - 2000m s.l.m.
Front panel protectionIP20
RISC microprocessor (32 bit)
Work frequency 200MHz
RAM 32MB
Flash 16MB

:info:Lengths in mm

3. Base card wiring

:tip:For details about cable sections and connectors, see application note AN021

.

:tip:The electrical features are described in the section Electrical features.
The wiring examples are given in section Connection examples

:important:The cabling must be carried out by specialist personnel and fitted with suitable anti-static precautions.
Before handling the controller, disconnect the power and all parts connected to it.
To guarantee compliance with EC regulations, the power supply must have a galvanic isolation of at least 1500Vac.

.

Power supply 24 Vdc
Voltage range 22 - 27 Vdc
Max. absorption 10W

Connector

CN1 TerminalSymbolDescription
1 DC power positive
2 GROUND Gnd-PE (signals)
3 DC power 0V

:important:Use an isolated power unit with 24Vdc +/-5% output conform to EN60950-1.

.

Use two separate power units: one for the control circuit and one for the power circuit
For a single power unit, use two separate lines: one for the control and one for the power
DO NOT use the same lines for the power circuit and the controller

PROG PORTDescription
Serial port used for the transfer and debugging of the application program in the CPU.
Use only with IQ009 or IQ013.
Connector
CN2 TerminalRS232RS422RS485Description
1A - - A Terminal A - RS485
2A - - B Terminal B - RS485
3A 0V 0V 0V USER PORT common
4A 0V 0V 0V USER PORT common
5A TX - - Terminal TX - RS232
6A Ground
1B - RX - Terminal RX - RS422
2B - RXN - Terminal RX N - RS422
3B - TX - Terminal TX - RS422
4B - TXN - Terminal TX N - RS422
5B RX - - Terminal RX - RS232
6B Ground
Setting USER PORT electric standard
SW2 Num.
Dip
Name
DIP
Setting
of DIP
Function
1 JP2 ON X2) X3) Termination RS485
2 JP3 ON X4) X5) Polarisation RS485
3 JP1 ON X6) X7)
4 OFF ON OFF Selection of USER PORT electric standard
5 ON OFF OFF
6 OFF OFF ON
RS485 RS422 RS2328)

1), 3), 4), 5), 6), 7) option not enabled
2) X = setting not significant
8) the USER PORT can be used as PROG PORT with RS232 electric standard, setting ON in DIP-8 of SW1 and OFF in DIP-6 of SW2

Connector
CN3 TerminalSymbolDescription
cnn_3fv_p3.5_03.jpg 1 0V RS485 serial common
2 B Terminal RS485 B
3 A Terminal RS485 A
Setup of AUX2 PORT polarisation and termination resistances
SW3 Num.
Dip
Name
Dip
Setting
of DIP
Function
dip-4.jpg 1 JP3 ON Polarisation RS485
2 JP2 ON Termination RS485
3 JP1 ON Polarisation RS485
4 X1) None

1) X = setting not significant

3.2.3.1 CANbus PORT

Connector
CN5
CAN1 PORT
TerminalSymbolDescription
cnn_3fv_p3.5_03.jpg 1 0V CAN common
2 CAN L Terminal CAN L
3 CAN H Terminal CAN H
Termination resistor setting
Name
jumper
Setting of DIPFunction
JP3 JP4
JP3 INSERTED Termination CAN active
JP4
Connector
CN4
CAN2 PORT
TerminalSymbolDescription
cnn_3fv_p3.5_03.jpg 1 0V CAN common
2 CAN L Terminal CAN L
3 CAN H Terminal CAN H
Termination resistor setting
Name
jumper
Setting of DIPFunction
JP1 JP2
JP1 INSERTED Termination CAN active
JP2

ETHERNET PORTDescription
Connector RJ45.

LED:
* LINK: green led = cable connected (led on signals the cable is connected to both ends)
* DATA: yellow led = data transmission (flashing led signals data transmission)

Memory card slot (marked by an arrow)

CN7 TerminalSymbolDescriptionAddres
1 0V Common for digital inputs
2 I1 Input I1 2.INP01
3 I2 Input I2 2.INP02
4 I3 Input I3 2.INP03
5 I4 Input I4 2.INP04
6 I5 Input I5 2.INP05
7 I6 Input I6 2.INP06
8 I7 Input I7 2.INP07
9 I8 Input I8 2.INP08

.

CN6 TerminalSymbolDescriptionAddress
1 0V Common for digital inputs
2 I9 Input I9 2.INP09
3 I10 Input I10 2.INP10
4 I11 Input I11 2.INP11
5 I12 Input I12 2.INP12
6 I13 Input I13 2.INP13
7 I14 Input I14 2.INP14
8 I15 Input I15 2.INP15
9 I16 Input I16 2.INP16

CN14 Terminal Symbol Description Address

1A Output + 24V dc1)
2A PHA1 Phase A Count 1
PNP / Push-Pull2)
2.INP17 2.CNT01
3A PHB1 Phase B 2.INP18
4A Z1 Z 1.INT01
5A 0V Common for count inputs
6A 0V
7A 0V
1B Output + 24V dc3)
2B PHA1+ + PHA Count 1
Line Driver
2.INP17 2.CNT01
3B PHB1+ + PHB 2.INP18
4B Z1+ + Z 1.INT01
5B PHA1- - PHA
6B PHB1- - PHB
7B Z1- - Z

1), 3) Used to power the encoder. See Connection examples.
2) PNP/Push-Pull type count input configuration:
Terminal 5B: connect to terminal 5A
Terminal 6B: connect to terminal 6A
Terminal 7B: connect to terminal 7A
CN15 Terminal Symbol Description Address

1A Output + 24V dc1)
2A PHA2 Phase A Count 2
PNP / Push-Pull2)
2.INP19 2.CNT02
3A PHB2 Phase B 2.INP20
4A Z2 Z 1.INT02
5A 0V Common for count inputs
6A 0V
7A 0V
1B Output + 24V dc3)
2B PHA2+ + PHA Count 2
Line Driver
2.INP19 2.CNT02
3B PHB2+ + PHB 2.INP20
4B Z2+ + Z 1.INT02
5B PHA2- - PHA
6B PHB2- - PHB
7B Z2- - Z

1), 3) Used to power the encoder. See Connection examples.
2) PNP/Push-Pull type count input configuration:
Terminal 5B: connect to terminal 5A
Terminal 6B: connect to terminal 6A
Terminal 7B: connect to terminal 7A

CN16 Terminal Symbol Description Address

1A Output + 24V dc1)
2A PHA3 Phase A Count 3
PNP / Push-Pull2)
2.INP21 2.CNT03
3A PHB3 Phase B 2.INP22
4A Z3 Z 1.INT03 FREQ13)
5A 0V Common for count inputs
6A 0V
7A 0V
1B Output + 24V dc4)
2B PHA3+ + PHA Count 3
Line Driver
2.INP21 2.CNT03
3B PHB3+ + PHB 2.INP22
4B Z3+ + Z 1.INT03 FREQ15)
5B PHA3- - PHA
6B PHB3- - PHB
7B Z3- - Z

1), 4) Used to power the encoder. See Connection examples.
2) PNP/Push-Pull type count input configuration:
Terminal 5B: connect to terminal 5A
Terminal 6B: connect to terminal 6A
Terminal 7B: connect to terminal 7A
3), 5) Can be used as frequency input for a FREQ device, indicating 1 in the device declaration
CN17 Terminal Symbol Description Address

1A Output + 24V dc1)
2A PHA4 Phase A Count 4
PNP / Push-Pull2)
2.INP23 2.CNT04
3A PHB4 Phase B 2.INP24
4A Z4 Z 1.INT04 FREQ23)
5A 0V Common for count inputs
6A 0V
7A 0V
1B Output + 24V dc4)
2B PHA4+ + PHA Count 4
Line Driver
2.INP23 2.CNT04
3B PHB4+ + PHB 2.INP24
4B Z4+ + Z 1.INT04 FREQ25)
5B PHA4- - PHA
6B PHB4- - PHB
7B Z4- - Z

1), 4) Used to power the encoder. See Connection examples.
2) PNP/Push-Pull type count input configuration:
Terminal 5B: connect to terminal 5A
Terminal 6B: connect to terminal 6A
Terminal 7B: connect to terminal 7A
3), 5) Can be used as frequency input for a FREQ device, indicating 2 in the device declaration

CN11 Terminal Symbol Description Address
1A Internal bridge 1A-2A-1B-2B
2A
3A DATA1+ DATA in SSI1 1
4A DATA1-
5A CLOCK1+ CLOCK out SSI1
6A CLOCK1-
7A 0V Common for count inputs
1B Internal bridge 1A-2A-1B-2B
2B
3B DATA2+ DATA in SSI2 2
4B DATA2-
5B CLOCK2+ CLOCK out SSI1
6B CLOCK2-
7B 0V Common for count inputs

Connector

CN13 Terminal Symbol Description Address
Potenziometers / 0-10V / 0-20mA Thermocouple PT100
1 AI2_C - TC 2 + C 2.AI02
2 AI2_B - TC 2 - B
3 AI2_A Analog input 2 - A 1)
4 AI1_C - TC 1 + C 2.AI01
5 AI1_B - TC 1 - B
6 AI1_A Analog input 1 - A 2)
7 VREF Reference voltage 3) - -
8 GAI Common - -

1), 2) FIXME A and B cables are connected to the same head of the PT100 wire and have the same colors.
In the case of 2-wire PT100 make a jumper between A and B.
3) For potentiometers

Analog inputs setting

Num.
Dip
Analog input 1 Analog input 2
PT100 Thermocouple Pot. 0-10V 0-20mA PT100 Thermocouple Pot. 0-10V 0-20mA
SW5
dip-8.jpg
1 ON X OFF OFF OFF X X X X X
2 OFF X ON ON ON X X X X X
3 X X X X X ON X OFF OFF OFF
4 X X X X X OFF X ON ON ON
5 ON ON OFF OFF OFF X X X X X
6 OFF OFF ON ON ON X X X X X
7 OFF ON X X X X X X X X
8 X X X X X OFF ON X X X
SW4
dip-4.jpg
1 X X X X X X X OFF OFF ON
2 X X X X X X X OFF ON OFF
3 X X OFF OFF ON X X X X X
4 X X OFF ON OFF X X X X X

X = irrelevant setting
Pot. = potentiometric type input

CN9 TerminalSymbolDescriptionAddress
1 V+ Outputs power input O1÷O4 (12÷28V dc)
2 O1 Digital output 12.OUT01
3 O2 Digital output 22.OUT02
4 O3 Digital output 3 2.OUT03
5 O4 Digital output 4 2.OUT04
6 V+ Outputs power input O5÷O8(12÷28V dc)
7 O5 Digital output 5 2.OUT05
8 O6 Digital output 6 2.OUT06
9 O7 Digital output 7 2.OUT07
10 O8 Digital output 82.OUT08
11 V- Outputs power in (0V dc)

.

CN8 TerminalSymbolDescriptionAddress
1 V+ Outputs power input O9÷O12(12÷28V dc)
2 O9 Digital output 92.OUT09
3 O10 Digital output 102.OUT10
4 O11 Digital output 11 2.OUT11
5 O12 Digital output 12 2.OUT12
6 V+ Outputs power input O13÷O16(12÷28V dc)
7 O13 Digital output 13 2.OUT13
8 O14 Digital output 14 2.OUT14
9 O15 Digital output 15 2.OUT15
10 O16 Digital output 162.OUT16
11 V- Outputs power in (0V dc)

Connector

CN10 TerminalSymbolDescriptionAddress
1A VD1 Internal bridge 1A -1B
2A DIR1+ Output DIRECTION 1Push-Pull Line Driver2.PULSE01
3A STEP1+ Output STEP 1
4A DIR2+ Output DIRECTION 2 2.PULSE02
5A STEP2+ Output STEP 2
6A 0V Common for stepper outputs
1B VD1 Internal bridge 1A -1B
2B DIR1- Complementary output DIRECTION 1Complementary outputs for use in drives with Line-Driver inputs
3B STEP1- Complementary output STEP 1
4B DIR2- Complementary output DIRECTION 2
5B STEP2- Complementary output STEP 2
6B 0V Common for stepper outputs

Outputs STEP-DIRECTION voltage setting

By placing one of several jumpers JP5, JP6 and JP7, you can choose Nominal Operating Voltage of STEP and DIRECTION outputs.

:important:Must be inserted only one jumper at a time
If you select one of the two voltage 5V (JP7) or 12V (JP5) terminals 1A and 1B must remain disconnected

.

jumper
name
Setting Nominal voltage
JP5 INSERTED 12V (Voltage supplied by the instrument)

JP6 INSERTED VD1 (Voltage to be supplied to the terminals 1A or 1B)
JP7 INSERTED 5V (Voltage supplied by the instrument)

CN12 TerminalSymbolDescriptionAddress
cnn_6fv_p3.5_01.jpg 1 GAO Common for analog outputs
2 AO1 Analog output 12.AN01
3 AO2 Analog output 22.AN02
4 GAO Common for analog outputs
5 AO3 Analog output 32.AN03
6 AO4 Analog output 42.AN04

4. Electrical features

The electrical features of the hardware are given below. Maximum and minimum frequency values and actual acquisition times, can still depend on any additional software filters, see for example the system “QMOVE:sys004” variable on the section “QMOVE:sys004” on the section System variables.

Connector for IQ009 or IQ013

:important: The USB mini-B connector does not support USB electrical standards, it can only be used with an interface IQ009 or IQ013.

It is used for the transfer and debugging of the application program in the CPU.

Electrical standard TTL (Use serial interface IQ009 or IQ013)
Communication speedMin. 9.6 Kbaud - max 115200 Kbaud
settable by dip1 and 2 of the switch SW1
InsulationNone

.

Connection between Qmove+ e PC using the accessory IQ009

.

Connection between Qmove+ and a device fitted with a RS232 serial port (e.g. a MODEM), using the interface IQ013

Communication speed4800, 9600, 19200, 38400, 57600, 115200 baud
Communication modeFull duplex
Operating modeReferred to 0V
Max. number of devices connected on the line1
Max. cable length15 m
Input impedence> 3 Kohm
Short-circuit current limit7 mA

Internal wiring diagram of RS232

Cable connection diagram of RS232

Communication speed4800, 9600, 19200, 38400, 57600, 115200 baud
Communication modeFull duplex
Operating modeDifferential
Max. number of devices connected on the line1
Max. cable length1200 m
Input impedence> 12 Kohm
Short-circuit current limit35 mA

Internal wiring diagram of RS422

Cable connection diagram of RS422

Cable connection diagram of RS422

.

Communication speed4800 baud (only if used with SERCOM and/or MODBUS device),
9600 baud, 19200 baud, 38400 baud, 57600 baud
Communication modeHalf duplex
Operating modeDifferential
Max. number of devices connected on the line32
Max. cable length1200 m
Input impedence> 12 Kohm
Short-circuit current limit35 mA

Internal wiring diagram of RS485

Cable connection diagram of RS485

:info:To activate the internal termination resistance see section Terminating resistors setting CAN1 and CAN2 PORT

.

Comunication speed125, 250, 500, 1000 Kbit/s
Maximum numr of Drivers/Receiver on the line100
Maximum cable length500m @ 125Kbit/s, 250m @ 250Kbit/s, 100m @ 500Kbit/s, 25m @ 1000Kbit/s
Input impedance>15Kohm
Short circuit current limit45mA

Canbus internal diagram

Canbus connection cable diagram

:important: On the first and last device, must be insert the termination resistance.

Ethernet Interface 10/100 Base T (IEEE 802.3) on RJ45 connector.

Connection between Qmove + and PC:

Qmove+ Cross-over cable EIA/TIA-568A/B PC

Type of Memory Card to useMMC, SD and SDHC up to 8GB
For proper operation it is necessary that the device conforms to the standards set by “SD Association” (www.sdcard.org) or “Multi Media Card Association” (www.mmca.org).

.

:important:To use the Memory Cards they must first be formatted with FAT16 or FAT32 file system.

Max output current500mA

Type of polarisation PNP
Min. acquisition time (hardware) 3ms
Isolation 1000Vrms
Rated operating voltage 24Vdc
Voltage of logic state 0 0-2 V
Voltage of logic state 1 10.5 - 26.5 V
Internal voltage drop 5V
Input resistance (Ri) 2700Ω
Sink current2mA ÷ 8mA1)

1) CAUTION: If the device connected to the inputs needs a higher minimum current, inputs may not work properly.

Internal diagram of standard digital input.

The values given in the table refer to input signals A, B and Z.
The max. frequency given in the table refers to A and B phase signals with a DutyCycle = 50%
With count frequencies over 50KHz the use of Line-Driver type encoders is recommended.

Type of polarisation PNP/PP
Max frequency 200KHz
Min. acquisition time 5µs
Insulation 1000Vrms
Rated operating voltage 24Vdc
Voltage of logic status 0 0 - 2 V
Voltage of logic status 1 10.5 - 26.5 V
Internal voltage drop 1.2V
Input resistance 3100Ω

Line-Driver

Type of polarisation Line-Driver
Max. frequency 200KHz
Min. acquisition time 5µs
Insulation 1000Vrms
Rated operating voltage (PHx+ ? PHx-) 5Vdc
Voltage of logic status 0 (PHx+ ? PHx-) 0-1.5 V
Voltage of logic status 1 (PHx+ ? PHx-) 2-5 V
Internal voltage drop 1.2V
Input restistance 150Ω

Internal diagram of count inputs.

Frequency 320KHz
Operation mode Differential
Input impedance >= 12KO
Short circuit current limit >= 35mA

SSI internal diagram

The electrical features depend on the type of input, configurable via DIP switch.

The conversion times from analog to digital depend on the configuration according to the table:

Analog Input Configuration Conversion time
per channel
Input 1 Input 2
DC1) - 4.6 ms
- DC2) 4.6 ms
DC3) DC4) 9.3 ms
DC5) TC 9.3 ms
DC6) PT100 79.1 ms
TC - 9.3 ms
- TC 9.3 ms
TC DC7) 9.3 ms
TC TC 9.3 ms
TC PT100 83.8 ms
PT100 - 74.5 ms
- PT100 74.5 ms
PT100 DC8) 79.1 ms
PT100 TC 79.1 ms
PT100 PT100 79.1 ms

1), 2), 3), 4), 5), 6), 7), 8) Amperometric, voltmetric or potentiometric type
Connection type Amperometric
(0-20 mA)
Resolution 12bit/16bit1)
Input resistance 125Ω
Value of damage 25 mA
Max. Linearity error + 0,1% Vfs
Max. Offset error + 0,1% Vfs
S.n. 71 dB
Conversion time It depends on the configuration of the analog input.
See section Conversion times if present 2)
Isolation 1000 Vrms

1) It depends on the Hardware versions
2) The sampling time of the device must be equal or higher than the conversion time

Amperometric analog input internal scheme

Connection type Potentiometric 1KΩ÷20KΩ
Resolution 12bit/16bit1)
Reference voltage output 2,5Vdc
Max output current from reference 10mA
Input resistance 10MΩ
Max. Linearity error + 0,1% Vfs
Max. Offset error + 0,1% Vfs
S.n. 71 dB
Conversion time It depends on the configuration of the analog input.
See section Conversion times if present 2)
Isolation 1000 Vrms

1) It depend on the Hardware versions
2) The sampling time of the device must be equal or higher than the conversion time

Potentiometric analog input internal scheme

Connection type Voltmetrico
0÷10V
Resolution 12bit/16bit1)
Input resistance (Rin) 40KΩ
Value of damage 20V
Max. Linearity error + 0,1% Vfs
Max. Offset error + 0,1% Vfs
S.n. 71 dB
Conversion time It depends on the configuration of the analog input.
See section Conversion times if present 2)
Isolation 1000 Vrms

1) It depends on the Hardware versions
2) The sampling time of the device must be equal or higher than the conversion time

Voltmetric analog input internal scheme

Sensor type
collegabile
PT100 3 wire 1)
Measure type Resistance 2)
Resolution 15 bit (32767 corresponds to 250.00 O)
Input resistance (Rin) 15 MO
Measuring current 1 mA
Value of damage 10V
Accuracy of resistance measurement ± 0,04%
Conversion time It depends on the configuration of the analog input.
See section Conversion times if present 3)
Isolation 1000 Vrms

1) Also connected to 2-wire terminals with jumper
2) Temperature calculated by software
3) The sampling time of the device must be equal or higher than the conversion time

Sensor type Thermocouple type J,K,R,S,B,N,T,E 1)
Type of measure Differential voltage
Resolution 16 bit
Measuring range ±156.25 mV
Measure for cold junction compensation Integrated
Input resistance (Rin) 15 MO
Value of damage 30V
Measurement accuracy ± 0,2% (excluding cold junction compensation)
Conversion time It depends on the configuration of the analog input.
See section Conversion times if present 2)
Isolation 1000 Vrms

1) J and K only supported by SW. Contact QEM for the support of the other sensor types.
2) The sampling time of the device must be equal or higher than the conversion time

Switchable load Dc (PNP)
Max. operating voltage 28V
Insulation 1000Vpp
Max. internal voltage drop 600mV
Max internal resistance @ON 90mΩ
Max. protection current 12A
Max. operating current 2A
Max. current @OFF 5µA
Max switching time from ON to OFF 270µs
Max switching time from OFF to ON 250µs

Internal diagram of protected outputs

Type of polarisation Push-Pull / Line-Driver
Max output frequency 200KHz
Insulation 1000Vpp
Max. operating current 20mA
Max. voltage 24Vdc1)

1) Selectable via jumpers: 5V e 12V supplied by the instrument, 24V supply from outside to the terminal VDx

Internal diagram outputs control stepper motors

Type of connection Common mode
Insulation 1000Vrms
Voltage range (minimum no load) -9.8V - +9.8V
Max. offset variation depending on temperature* +/- 5mV
Resolution 16bit
Max. current 1mA
Output variation depending on load 100 µV/mA
Output resistence 249Ω

Internal diagram of analog outputs

5. Connection examples

Esempio di collegamento dei moduli remotati al controllore

:important:On the first (1) and on the last (3) device of the chain, the termination resistances must be inserted.
The cable shoes must be connected to ground by the fastons provided on the metal body.

.

:info:To activate the internal termination resistance see paragraph Setup of CAN1 and CAN2 PORT Termination resistances

CANbus connection example

:important:Caution: close the DIP JP1 and JP2 and insert the terminating resistors (RL, RH) on the last device in the chain.

Standard and rapid PNP inputs, connection examples

Line Driver counter input connection examples

PNP / Push Pull counter input connection examples

SSI absolute counter connection examples

Protected digital output connection examples

STEP - DIRECTION output connection examples

Example with Push-Pull Output 1 and Line-Driver Output 2

Analog output connection examples

6. Settings, procedures and signals

Rear view to identify the devices illustrated in this chapter

SW1 Dip DIP Settings Function
dip-8.jpg 1 OFF Baud-rate 57600 PROG PORT transmission speed selection
ON Baud-rate 115200
2 OFF Baud-rate 57600 USER PORT transmission speed selection
ON Baud-rate 115200
3 OFF Can also be used by SERCOM and MODBUS device PROG PORT function mode selection
ON Cannot be used by SERCOM and MODBUS device
4 OFF ON OFF ON Valid if in the CANOPEN device declaration is set the speed to 0 )]
5 OFF OFF ON ON
Baud-rate
125KB/S
Baud-rate
250KB/S
Baud-rate
500KB/S
Baud-rate
1MB/S
6 OFF MMC/SD External media device selection on the system functions
ON USB
7 Reserved. Leave OFF
8 OFF PROG PORT normal Select the USER PORT as PROG PORT1)
ON PROG PORT on the USER PORT connector

1) It's possible to use the connector of the USER PORT as PROG PORT with RS232 electric standard. The mini-USB PROG PORT connector is unplugged (USER PORT electric standard setting). For this function is necessary to set at OFF the dip 6 of the SW2.

The system leds “pow, run, stop, err” are found on the front panel and on the rear of controllers with display and only on the top of controllers without display.

The user leds “L1, L2, L3 e L4” are found on the rear:

Leggend:

led_on.jpg Led ON

led_off.jpg Led OFF

led_lamp.jpg Led Blinking

LedColourStatusDescription
powGreenled_on.jpgPower on
led_on.jpgOnly this led on, signals the CPU reset status
runGreenled_on.jpgCPU in RUN status
led_lamp.jpgCPU in READY status
stopYellowled_on.jpgWith pow on, signals the STOP status of the CPU
With pow off, signals the BOOT status of the CPU
errRedled_lamp.jpgWith pow off, signals a hardware error. See paragraph Hardware Error codes
With pow blinking, the flash rate gives the type of error. See paragraph err led signals

Err led signals

N.
flashes
ErrorDescriptionRecommended action
1 Bus errorBus configuration different to application software.Check the correspondence between the QMOVE application (BUS section of configuration unit) and the product configurations (cards mounted in BUS).
2 CheckSum ErrorNegative outcome on the integrity control of retentive variables . (see Reset Error Checksum)Restore the machine data from a backup (.DAT file) or cancel the error with in system functions and enter the values manually.
3 Index Out of BoundAn array index is pointing on an inexistent elementOpen a unit editor in Qview development environment and use the “Edit→Go to PC” command to find the program line that is cause of the error. In general the index value has a value <1 or >array dimension.
4 Program Over RangeThe program selection index in the DATAGROUP has attempted to access an inexistent program.With the Qview development environment open the editor of a unit and user the “Edit→Go to PC” command to highlight the program line that has caused the error. In general the value used as index is lower than 1 or over the array dimension.
5 Step Over RangeThe step selection index in the DATAGROUP has attempted to access an inexistent step.With the Qview development environment open the editor of a unit and user the “Edit→Go to PC” command to highlight the program line that has caused the error. In general the value used as index is lower than 1 or over the array dimension.
6 Division By ZeroThe denominator of a division operation of the application program has a zero value.With the Qview development environment open the editor of a unit and user the “Edit→Go to PC” command to highlight the program line that has caused the error.
7 Syntax ErrorThe application program has an invalid instructionThis error may appear because the program counter has met the QCL END instruction.
8 Watch Dog ErrorA CAN module does not function correctly, or a specialist card has a hardware problemWith the Qview development environment open the “Monitor→Bus” panel and the righthand column called “Watchdog Bus” indicates the card that caused the problem.
9 Stack ErrorThe applciation program has used all permitted levels of calls to subroutinesWith the Qview software environment open the editor of a unit and use the “Edit→Go to PC” command to highlight the program line that caused the error. Analyse the unit execution flow, the call to subroutines nestings have a limit, over which this error is generated.

Hardware error codes

During the startup sequence, if a malfunction of any peripheral is detected, the system blocks and the error is signaled by the flashing led led_lamp.jpgerr while the other system led's remain off.

The number of flashes indicates the type of error according to the following table :

Number of flashesError
1 Display
2 FPGA
3 Media
4 Bootloader
5 FW
6 Bus
7 Signal not active
8 Signal not active
9 Exception

.

:important:Each of these signals indicates a serious error situation. The product must be sent to the QEM aftersales service.

LedColourDescription
led_on.jpg L1YellowProgrammable in the application program by the QMOVE system variable:sys003 and used by the system functions
led_on.jpg L2
led_on.jpg L3
led_on.jpg L4

NameDescription
pulsante_6x6.jpgFUNCPress on startup of the controller to access the System functions
pulsante_6x6.jpgBOOTPress on startup of the controller to set the CPU in Boot status and then access the firmware update functions
pulsante_6x6.jpgRESETReset CPU. the system is restarted restoring the initial conditions (after a startup )

7. Operating Overview

This chapter covers aspects and descriptions of the product functionalities that are often related to the firmware, which enable the functionalities that enable its operation as a QEM Qmove+ programmable system.

To best understand the terms used in this chapter, it is important to know the organisation of data and memory in a QMOVE application. QMOVE applications are programs written in QCL language that, translated in binary code, are transferred onto QMOVE hardware and saved there. In the hardware, the microprocessor runs has a program called firmware that interprets the above binary code instructions and performs the operations associated to them.

A QCL application, in addition to the instructions, is also composed of variables that the QCL instructions act on.. Some of these variables are retentive, i.e. their values remain unaltered from shut-off to start up. The flow chart below illustrates the organisation of data in a QCL application transferred to the memory of any QMOVE hardware:

It can be noted that, the QMOVE hardware has several mass storage devices:

“Flash memory”, where the following is saved:

  • QCL program: the series of QCL instructions translated into binary by the compiler.
  • HMI program: the series of HMI screens translated into binary by the compiler. This program only exists when the QMOVE hardware has a display.
  • Configuration data: the calibration and configuration data, the touch-screen calibration settings, the ethernet communication configuration data (IP address, etc…), etc.

“Non volatile memory”, which stores:

  • Retentive variables: the group of variables that remains unaltered on a shut-off and startup (e.g. SYSTEM, ARRAYS, DATAGROUP, etc).

“Volatile memory”, which stores:

  • Not retentive variables: the group of variables that is set to 0 at each startup (e.g. GLOBAL, ARRGBL, etc).

The volatile data memory is also used as dynamic memory. i.e. the memory used by the firmware for internal operations and active HMI screen management.

“Mass storage internal device” is managed by a standard filesystem and is useful to save information by the DATASTORE device (read - write binary or csv files with recipes, logs, variuous setups, etc).
It 'also used to store the backup of the application QMOVE and other service files.

“Mass storage external device” is managed by a standard filesystem and is useful for loading the QMOVE application, data loading/saving, firmware update or to save informations by the DATASTORE device.

The CPU has several operating statuses. The figure below shows the main status changes from the controller startup.
The main operating statuses are RESET, READY, RUN and STOP.
The CPU events that determine a transition from one status to another are mainly linked to commands being sent by the development environment: Run, Reset, Stop and Restart.
Application download is the development environment procedure that allows to transfer a QMOVE application to the CPU.

Stati della CPU

The BOOT state can be used to access the firmware updating functions.

During the startup, after scanning the system led's, the controller performs a series of self-diagnostic operations. When any faults are detected or the operator has to be informed of any given situation, the self-doagnosis procedure is temporarily interrupted, signalling the event.
The fault signal is made by led's L1, L2 and a message is given on display (if present).

System Messages
n.Led ONSystem Message (if display present)DescriptionType
1led_on.jpg L1System Data WRITE ERRORIndicates that a write error has occurred during the configuration data saving. B
2led_on.jpg L2System Data IS RESTORED FROM DEFAULTIndicates that the configuration data has been restores to the default settings. C
3led_on.jpg L1
led_on.jpg L2
System Data is updated
Please verify new data
Indicates that the configuration data has been converted into a new format. Check that the previous settings have been maintained. C
4led_on.jpg L3Firmware is updated
old: 1K31F10 1.001
new: 1K31F10 1.002
Indicates that a firmware update has been made. C

When the condition detected allows to continue to the start stage (type C) and waits for the FUNC button or for the F1 key to be pressed to continue the boot procedure.

If not provided with a display, the controller waits 5 seconds before continuing with the startup stage, without waiting for a button to be pressed.

When the situation does not allow to continue the startup stage (tipo B), the controller, if provided with a display, shows the message“PLEASE TURN OFF AND TURN ON THE SYSTEM” and remains in this state until you turn off. If the controller is not provided with a display, the led led_lamp.jpg err flashes continuously.

The SYSTEM FUNCTIONS status can be used to access the SYSTEM FUNCTIONS, which are special procedures that allow the user to perform various operations. For more details see the System Functions chapter.



Led statusled_on.jpgpow
led_off.jpgrun
Status causeNo application in memory.
The condition that can put the CPU in this statusRESET command.

This condition can only pass onto a READY status by downloading the applicaiton, using the Qview6 development environment.



Led statusled_on.jpgpow
led_lamp.jpgrun
Status causeApplication valid and waiting for execution.
Conditions that can put the CPU in this statusApplication download.

This condition can pass onto to the RUN or RESET statuses.



Led statusled_on.jpgpow
led_on.jpgrun
Status causeApplication in execution.
Condition that can put the CPU in this statusRUN command.

This condition can pass onto all other CPU statuses.



Led statusled_on.jpgpow
led_on.jpgstop » led_off.jpgrun
Status causeStop on application in execution.
Condition that can put the CPU in this statusA breakpoint has been encountered in the application code interpretation.

This condition can pass onto all other CPU statuses.

:important:IMPORTANT: The use of these procedures could represent a risk (e.g. deletion of application), therefore it is highly recommended that they are performed by qualified experts.

The system functions are speficic procedures that allow the user to perform various operations, e.g. the configuration/calibration of peripherals, data and application save/restore on/from removable mass memory, deletion of the application and management of the mass memories.

All the system functions are listed below.
DEVICE indicates an external storage media. MMC / SD or USB for hardware that they have the port.

System Functions

n.Led ONSystem FunctionsDescription
1led_on.jpgL101 - Reset Error ChecksumReset checksum error.
NOTE: if the checksum error is present, the led led_on.jpg L1 flashes.
2led_on.jpgL202 - Copy all files DEVICE → NANDCopy all files from DEVICE to NAND Flash memory.
3led_on.jpgL1
led_on.jpgL2
03 - Copy all files NAND → DEVICECopy all files from NAND Flash memory to DEVICE.
4led_on.jpgL304 - Application deleteDelete the application.
5led_on.jpgL1
led_on.jpgL3
05 - Application upload from DEVICEUpload the application from DEVICE.
6led_on.jpgL2
led_on.jpgL3
06 - System SettingsNot implemented for this hardware
7led_on.jpgL1
led_on.jpgL2
led_on.jpgL3
07 - Downl. retentive data to DEVICESave the retentive data on DEVICE.
8led_on.jpgL408 - Set NEW PasswordNot implemented for this hardware
9led_on.jpgL1
led_on.jpgL4
09 - Remove all files from NAND FlashCancel all files stored on the NAND Flash memory.
10led_on.jpgL2
led_on.jpgL4
10 - Show NAND Flash filesNot implemented for this hardware
11led_on.jpgL1
led_on.jpgL2
led_on.jpgL4
11 - Touch CalibrationNot implemented for this hardware
12led_on.jpgL3
led_on.jpgL4
12 - Set Ethernet communic. parameterNot implemented for this hardware
13led_on.jpgL1
led_on.jpgL3
led_on.jpgL4
13 - Backup to NANDRun the backup of the QCL application, data and HMI application on NAND memory.
14led_on.jpgL2
led_on.jpgL3
led_on.jpgL4
14 - Restore from NANDRun the restore of the QCL application, data and HMI application from NAND memory.
15led_on.jpgL1
led_on.jpgL2
led_on.jpgL3
led_on.jpgL4
15 - Firmware UpgradeRun the firmware upgrade from DEVICE.
Available only in some hardware.

Note: To exit system functions press the keep the FUNC button for at least two seconds.

:tip:To access the System Functions, start up the controller with FUNC button pressed.

The QMOVE application, if present, it not executed and the led L1 lights up.

:tip:Use FUNC button to scroll through the functions.
The selected function is indicated by the combination of L1-L2-L3-L4 leds lighted up.

The “System Functions” table gives the list of system functions and related led combinations.

:tip:Press BOOT button for 2 seconds to execute the selected function.
The POW led starts flashing to indicate that the selected function is being executed.

When the function ends the POW led stops flashing.

:tip:Press FUNC button to restart the controller.

If the function does not complete properly the POW stops and the ERR starts flashing.

The number of flashes indicates the type of error as shown in the table System Function Error Messages.



When a system function ends with an error, the number of led flashes led_lamp.jpg err indicates the type of error.
If there is a display, a message is given to describe the cause of the error.

System Function Error Messages
Error/Number of ERR led flashesMessage
1 Generic error
2 Open/Exist/Create file error
3 Read file error
4 Write file error
5 Out of Memory error
6 QMos Version error
7 Checksum Error
8 Symbols checksum No Match
9 Configuration / Symbols error
10 File format error
11 Format error
12 Device not present or unformatted
13 Application not present error
14 Touch calibration failure
15 File compression type not support
16 Target don't match project !
17 Fw version don't match project !
18 File copy error
19 File size error
20 Crypt operation error
21 Invalid Product Serial Number
22 Function is locked
23 Function not enabled



The system runs an integrity control of retentive variables by the applicaiton of a CRC to the nonvolatile data memory. This detects any corruption and prevents the application from starting up, signalling the situation by flashing the led led_lamp.jpg err as shown in Err led signals.
For the application to function again, a new download of the application must be performed with the development environment, or the “Reset Error Checksum” system function. These operations delete the error status and zero-setsall retentive variables.

The procedure:

  • Check the error status and end the funciton if no error is present.
    In microQMove products, the presence of the QCL application is also checked.
  • Vengono azzerati i dati ritentivi e viene visualizzato il messaggio “Clear power down data…” fino al termine della procedura.
  • Resets the retentive data and the message “Clear power down data…” until the end of the procedure.
  • End of operation

This procedure copies all files in the root and “DS” directory of the external MMC/SD or USB card to the NAND internal mass storage.

The following table gives the sequence of operations and any possible errors:

MessageDescriptionPossible errors
Check DEVICE presenceChecking for the presence of the external mass storage card
On DEVICE appears MMC or USB, depending on what is selected
Device not present or unformatted
Mounting device…Mounting the external mass storage cardDevice not present or unformatted
Searching files…Searching for compatible filesNo Files Found
Copy <filename>….Making a copy of the files indicating the name currently in copy

This procedure copies all files contained in the root and “DS” directory of the NAND internal mass storage to the external MMC/SD or USB card memory.

The following table gives the sequence of operations and any possible errors:

MessageDescriptionPossible errors
Check DEVICE presenceChecking for the presence of the external mass storage card
On DEVICE appears MMC or USB, depending on what is selected
Device not present or unformatted
Mounting device…Mounting external mass storage deviceDevice not present or unformatted
Searching files…Searching for compatible filesNo Files Found
Copy <filename>….Copying the files indicating the name of the one currently in copy

This deletes the application and empties the nonvolatible data memory, deleting the QCL program and, if present, deleting the HMI program.

The following table gives the sequence of operations performed and any possible errors:

MessageDescriptionPossible errors
Reset retentive dataEmpty nonvolatible data memoryWrite file error
Delete QCL applicationDeletion of the QCL programWrite file error
Delete HMI applicationDelection of the HMI program (if display installed)Write file error



This loads an application from the external MMC/SD or USB mass memory card to the non volatile memory.

This allows to load all or one of the QCL program, HMI program and retentive data.

The external MMC/SD or USB mass memory card must contain at least one of the following files:

  • applic.bin for the compiled QCL program generated by the Qview development environment
  • applic.dat for the data file generated by the “Save Data…” procedure of the Qview development environment or by the Downl system function. for retentive data to DEVICE;
  • appqtp.bin for the compiled HMI program generated by the Qpaint development environment; it is generated by the special function “Download the project to File…”.
MessageDescriptionPossible errors
Check DEVICE presenceChecking for the presence of the external mass storage card
On DEVICE appears MMC or USB, depending on what is selected
Device not present or unformatted
Mounting device…Mounting external mass storage cardDevice not present or unformatted

If the applic.bin is present:

MessageDescriptionPossible errors
Upload QCL applicationUploading the QCL programOpen/Exist/Create file error
Write file error
Read file error
Out of Memory Error
QMos Version Error
Checksum Error
Symbols checksum No Match
Configuration / Symbols Error

If the applic.bin file is not present, an application must already be loaded in the nonvolatile memory otherwise the “Application not present” message is given.

If the applic.dat file is present:

MessageDescriptionPossible errors
Upload retentive dataUploading retentive data to the nonvolatile data memoryOpen/Exist/Create file error
Write file error
Read file error
Out of Memory Error
QMos Version Error
Checksum Error
Symbols checksum No Match
Configuration / Symbols Error
QTP File format error

The procedure performs the following steps:

  • Check the presence of the MMC/SD or USB card.
    The “Check DEVICE presence” message is given.
    On DEVICE appears MMC or USB, depending on what is selected.
  • Mounting MMC/SD or USB card.\\The “Mounting device…” message is given.
  • Uploading the QCL program (applic.bin), if contained in the removable mass storage device
    The “Upload QCL application” message is given.
  • Uploading retentive data of the QCL program (applic.dat), if contained in the removable mass storage device
    The “Upload retentive data” message is given.
    NOTE: if the applic.dat file is not found, the data in the system is maintained so long as the Symbol and Configuration checksums have not been varied. If they are varied all data will be set to zero.
  • Uploading the HMI program (appqtp.bin), if contained in the removable mass storage device
    The “Upload HMI application” message is given.
  • The file is closed and the operation ends.



This function creates a file on external mass storage (MMD/SD or USB) containing the retentive data values.
The file created is named “applic.dat” and is the same as the file obtained by the “Save Data…” procedure in the QView development environment. The function can only be performed if there is a valid QCL application in the controller.

The procedure performs the following steps:

  • Check the presence of the MMC/SD or USB card.
    The “Check DEVICE presence” message is given.
    On DEVICE appears MMC or USB, depending on what is selected.
  • Mounting the MMC/SD or USB card.
    The “Mounting device…” message is given.
  • Check the presence of the QCL program
    The “Checking application presence…” message is given.
  • Check the validity of the retentive data
    The “Checking retentive data…” message is given.
  • Open the applic.dat destination file on the external MMC/SD or USB card
    The “Open destination file…” message is given.
  • Write the headers in the destination file
    The “Write headers to destination file” message is given.
  • Write the retentive data in the destination file
    The “Write data to destination file”.
    NOTE: the percentage progress of the operation is given during this step
  • Close the file and end the operation



Delete all files contained on the internal NAND flash mass storage.
Unlike the “Format NAND Flash” function, this acts at a filesystem level aqnd can therefore be performed as many times as necessary.

The procedure performs the following steps:

  • Calculation of the number of files contained in the internal mass storage.
  • The “Searching files…” message is given.
  • If zero files are found, the “No Files Found” message is given and the function ends, otherwise the “Delete <filename>” is given indicating the delection of every file found.
  • Close the internal storage and end procedure



The backup procedure creates a copy of the QCL application in execution and a dump of the retentive data, as files saved in the NAND mass storage. The files created have the following names:

  • applic.qcy identifies the file containing the QCL application (CPU)
  • appdat.qcy identifies the file containing the retentive data of the QCL application

The procedure performs the following steps:

  • Check the presence of the QCL application.
  • Create and write in NAND the QCL application backup file: applic.qcy.
  • Check the presence and validity of retentive data of the QCL application.
  • Create and write in NAND the retentive data backup file of the QCL application: appdat.qcy.
  • Procedure end and system reboot.

The restore procedure allows to recover from the NAND mass storage, the saved backup files of the QCL application and an dump of the retentive data.

The procedure :

  • The NAND backup file of the QCL Application is read: applic.qcy.
  • The NAND backup file of the QCL Application retentive data is read : appdat.qcy.
  • Procedure end and system reboot.

Upgrade the firmware of the instrument through the external storage device MMC/SD or USB.

In the external storage device MMC / SD or USB must be present the following file:

  • firmware.a21

The procedure performs the following steps:

  • Check the presence of the MMC / SD or USB.
  • Firmware Update.
  • Closing the file and end operation.
  • Automatic restart of the instrument.



The use of system functions Backup to NAND and Restore from NAND allows to save in backup and restore a QMOVE application.

The backup and restore operations use the NAND internal memory device. The backup procedure creates a file copy of the QCL program, the HMI program (if the controller has a Qem display) and an image of the ritentive data.

The files created:

  • applic.qcy containing the QCL program (QCL App)
  • appdat.qcy containing the ritentive data image (QCL Dat)
  • appqtp.qcy containing the HMI program (QTP App)

The files are encrypted and only the controller that generated them can run the Restore procedure so as to safeguard unauthorised data copies. The backup file copied to external memory such as MMC/SD or USB card can be carried out with the system function Copy all NAND files -> DEVICE. A directory named “QBK” is created in the MMC/SD or USB that contains the above files. In the same way backup files can be transferred to the controller using the system function Copy all files DEVICE -> NAND. In this case, the files in the MMC/SD or USB must always be contained in the directory “QBK”.

Backup/restore is an important function that can be used in the following cases:

  1. to restore the QMOVE application to a known situation (the situation at the time of the backup), if data has been changed by an operator or if the machine data has been altered for any reason.
  2. when testing a new application, a backup can be made of the original, stable version. If the new application being tested is not satisfactory, the restore command will recover the original version.

In this chapter are collected all the product information for programming.

The product programming requires the Qview-6 environments to program the QCL code and if the product has a graphic display, also the QPaint-6 environment to design the screen graphics. Noth these softwares are available in the Qworkbench software package that can be downloaded as freeware from the Qem website (in “Support” section).

The contoller has 3 slots. The slots 4 to 32 can be declared and must be used to address recources installed in the Canopen modules.

To use the terminal in a product that has a display, you must declare under INTDEVICE the device MMIQ2.

INTDEVICE
   Hmi	MMIQ2	2

To program with the QPaint-6 development environment it is important to select the correct target. To do so, in the environment select ProjectTarget Configuration then select the right controller according to the ordering code.

Example of a statement of the BUS to use on the BUS unit's configuration:

BUS
   1	1R44F	10
   2	1QM4F	.

The firmware versione must coincide, and if available, the specialization card name to the 3 slot must be correct. See the dedicate section.

This paragraph looks at how to measure an estimate of use of the product's memories. The non volatile memory is available to memorise the QCL program and has a capacity of 1MB.
The memory space occupied is equal to the size of the .BIN file generated by Qview. The percentage memory occupied can be viewed in the CPU panel of Qview under “Used CODE memory”, or this information can be obtained from the value of parameter “sizeapp” of the QMOS device.

The non volatile data memory used to memorise retentive variables, has a capacity of 819KB.
The percentage memory occupied can be viewed in the CPU panel of Qview, under “Used RETENTIVE”, or this information can be obtained from the value of parameter “sizeret” of the QMOS device.

The volatile data memory used to memorise non ritentive variables has a capacity that depends on various factors.

The PROG and USER serial ports implement the QEM proprietary communication protocol called BIN1.

The SERCOM and MODBUS devices can be used with all communication serial ports including PROG PORT. Use the following number settings during the device declaration to select the communication channel:

  0		PROG PORT
  1		USER PORT
  2		AUX1 PORT
  3		AUX2 PORT    (if available for this hardware)

When the SERCOM and MODBUS devices use the PROG PORT or USER PORT, they address the channel only if the communication status of the device is open (st_opencom = 1). When the channel of the device is closed (st_opencom = 0) in the serial, the BIN1 protocol returns active. To force the BIN1 protocol on the PROG port (thereby preventing the SERCOM device from occupying the channel) active the SW1 dip 3.

When using the MODBUS RTU protocol on serial port AUX2 (if available in the hardware) with RS485 electric configuration, remember that when the serial port is transmitting, the controller maintains the channel (DE) active for a longer time than the “MODBUS RTU” specification. To this must be consider a minimum time of 5 milliseconds after which it is possible to receive a new message. Also the SERCOM device, when it ends a transmission, has the same time the channel is active (DE).

The Ethernet communication port use the transport protocol TCP/IP, where the BIN1 protocol packets are encapsulated within TCP/IP data packets. There are two active connections identified by two communication ports can be freely set in the communication parameters of the Ethernet port. If the instrument is provided with a display, these values are displayed and modified using the system function 12 - Set Ethernet communic. parameter. Other ways to view and set these figures can be realized through special programs available within the development environment (QConfigurator-1 and QConfigurator-2).

The port set in “Port nr.1:” represents a communication channel equivalent to PROG PORT. The port set in “Port nr.2:” represents a channel equivalente to USER PORT. The ports 3 e 4 are not used.

The Ethernet port can also be used to establish a communication type Modbus TCP/IP with other networked devices. In this case the channel that identifies the Ethernet port can be set by entering the number 43.

mdbs   MODBUS   2   43

The 3 channels of Ethernet communication port (two with BIN protocol and one MODBUS TCP/IP) can be active simultaneously.

When downloading the Qmove application, the QView-6 development environment can give error messages that are not described in the development environment manual. These errors are special and the description string given by QView-6 is generated directly by the firmware.

The table below describes possible error messages generated by the firmware.

Firmware error messages
Possible error messageDescription
Error: SYSTEM + ARRSYS + DATAGROUP + INTDEVICE size overflow by 234bytes.Given when the retentive variables exceed the maximum limit.
Error: serial port not avaliable in SERCOM or MODBUS device declaration.Given when the wrong number is used during the device declaration to select the communication channel.
Error: CANOPEN device required if you use more than 3 slots.In the BUS definition more than 3 slots are being used and so the application requests the use of Canopen modules. To manage this, a CANOPEN device must be declared.
Error: incorrect bus fault mode in CANOPEN declaration.The CANOPEN device declaration indicates a fault mode (last value in the declaration) that is not supported.
Error: incorrect canbus speed in CANOPEN declaration.The CANOPEN device declaration indicates an invalid speed.
Error: too much CANOPEN device declaration.Only one CANOPEN device can be declared.
Error: absol. encoder resource num in ABSCNT device declar. is not avail.The ABSCNT device declaration indicates an inexistent resource.
Error: COUNT in ABSCNT device declaration is not a simulated counter.The counter address used in the ABSCNT device declaration cannot be a simulated type (e.g. 1.CNT01).
QMos version error. Unsupported instructions set.One or more statements in the project QCL are not supported by the firmware.
Error: compression file type not support.The compression of the compiled QCL program is not supported by the firmware.
Error: too mutch slots in bus declarations.They were declared under BUS more slots than those allowed by the hardware.

L'ambiente di sviluppo mette a disposizione una serie di variabili predefinite che possono essere utilizzate precedendo al nome la parola chiave “QMOVE.”. Per esempio “QMOVE.is_suspend”, “QMOVE.sys001”, ecc. Lo scopo del presente paragrafo è illustrare le 16 variabili di sistema chiamate sys001÷sys016 il cui significato dipende dal firmware che si sta utilizzando.

sys001

Questa variabile a sola lettura indica lo stato dei pulsanti FUNC (bit 0) e BOOT (bit 1). I valori possibili sono dunque:
0 = nessun pulsante premuto.
1 = pulsante FUNC premuto.
2 = pulsante BOOT premuto.
3 = pulsanti FUNC e BOOT premuti.

sys002

Questa variabile permette la lettura dell'immagine del dip-switch SW1. L'immagine viene acquisita solo all'accensione del prodotto. Il bit 0 corrisponde al dip 1 e così via.

NB: Alcuni dip non sono collegati al microprocessore e quindi viene letto sempre al livello logico 0.

sys003

Questa variabile permette il comando del led L1-L2-L3-L4. Il bit 0 corrisponde a L1, il bit1 a L2 e così via.

sys004

Questa variabile permette l'impostazione del filtro anti-glitch ai segnali delle fasi nei contatori bidirezionali. Il valore è espresso in KHz e si riferisce alla frequenza del segnale di una fase. Il range di valori ammesso è 30÷220. Il valore impostato di default é 220KHz. La variabile può essere anche riletta. La modifica del filtro può essere fatta in qualsiasi momento.

sys005÷16

Non utilizzata.

The device term identifies a category of software capable of supporting and monitoring activities, more or less complex, to solve the automation systems problems.
The list of implemented devices in the firmware depends from the firmware version.

The firmware version 10 include following device:

Device nameMinimum sampling
time (msec)
Maximum sampling
time (msec)
Execution time (%)
ABSCNT12508,31
ANINP125014,25
CALENDAR--0
CANOPEN1250100
COUNTER312505,94
DAC--0
DATASTORE1208,31
FREQ12504,75
MODBUS125032,07
QMOS--0
RECDATA12505,34
SERCOM12509,26

The firmware version 20 include also following device:

Device nameMinimum sampling
time (msec)
Maximum sampling
time (msec)
Execution time (%)
ANPOS212508,31
EANPOS125055,94
HEAD2125023,75
OOPOS3125027,91

The firmware version 30 include also following device:

Device nameMinimum sampling
time (msec)
Maximum sampling
time (msec)
Execution time (%)
CAMMING3125055,94
INTERP125035,63

7.5.4.1 Features of the device

This section describes the additional information of the devices. This information complement and complete the maintenance manual of the device available on the Qem site. These are the information related to the implementation of the devices in this product.

7.5.4.1.1 CANOPEN

If in the device declaration CANOPEN viene indicata la velocità zero allora essa diventa impostabile tramite dip di SW1.
The first slot of the target resources that reside within the Canopen is the 4.
The firmware capture the input interrupt while this is located in a Canopen module.
You can enter the 2 value in the Declaration of the device on the relative sector to the port. This setting makes it possible for the startup of the QCL DS402 drives through a request (QDO number 10). This function is essential in cases where there are driver without enable input and the power supply logical is in common with main power supply. If the main power supply is turn off, the drive ot communicating in CANOPEN because also the logic section are turned off.

7.5.4.1.2 DATASTORE

The files used from the device DATASTORE are contain in the /DS folder. If this folder does not exist it is created automatically.
The DATASTORE device can can operate with MMC/SD or USB NAND memory inside the product (not removable). To define how your device used the parameter value priority (0=MMC/SD, 1=NAND, 2=USB). If your application needs to frequently access to the MMC/SD or USB device and do not require physical removal, you can use a particular priority parameter setting that avoids continually MOUNT UMOUNT devices. Before execute the UMOUNT command to set the “priority = -1”.

A QCL code example to change device may be:

SUB SETMMC
  WAIT NOT data.st_busy
  IF data.st_mount
    data.priority = -1
    data.UMOUNT
    WAIT NOT data.st_mount
    CALL CHECK_ERR_WRN
  ENDIF
  data.priority = 0
  data.MOUNT
  WAIT data.st_mount
ENDSUB
 
SUB SETNAND
  WAIT NOT data.st_busy
  IF data.st_mount
    data.priority = -1
    data.UMOUNT
    WAIT NOT data.st_mount
    CALL CHECK_ERR_WRN
  ENDIF
  data.priority = 1
  data.MOUNT
  WAIT data.st_mount
  CALL CHECK_ERR_WRN
ENDSUB

Check for the existence of a file on the external memory. Do you use the “filenum” set to the -1 value and use the OPENFILE command. If you set again the -1 value in “filenum” and use the OPENFILE command will search for the name of the next file, and so on. Whenever we will use a different -1 value with OPENFILE the search loop filenum will be closes. When the search is complete and there will be no more files, then the device will response to the OPENFILE command “filenum = -2”. The successful execution of the command will be indicated by flag st_busy = 0. If the file extension is not HEX or CSV file itself is ignored by the search. In the case that the file name is not compatible with those managed by DATASTORE (numbers from 0 to 9999999) then the “filenum” will remain set to -1 value and will report a warning.

The “disksize” and “diskfree” parameters are represented in KB.

7.5.4.1.3 RECDATA

The device can store 10000 step maximum.

7.5.4.1.4 QMOS

The “frwuvalue01” parameter contains the numeric value of the serial number of the product.
The “frwuvalue02” parameter contains the numeric value of the PN (Part Number).
The “frwuvalue03” parameter contains the numeric value of the hardware release.
The “frwuvalue04” parameter contains the numeric value of the VN (Vedi Nota).
The “frwuvalue05” parameter contains the numeric values of the QCL Level.

7.5.4.1.5 FREQ

To define the input associated to the device FREQ use the appropriate numeric field on the device. The availability of frequency inputs must be verified with the hardware version of the product. To derive the relationship between numerical value and terminal pin use the information in the “address” column in the tables in the illustration of the terminal.

7.5.4.1.6 CAMMING3

The parameters in the fields sector (CodeQm, CodeQs…) are not ritentive. At power-up they take always value 0.

8. Available accessories