This is an old revision of the document!
Specialization card 1AD2F rel.03
Informations
Document: | MIM1AD2F02 | |||
---|---|---|---|---|
Description: | Installation and maintenance manual | |||
Editor: | Riccardo Furlato | |||
Approver | Gabriele Bazzi | |||
Link: | http://www.qem.eu/doku/doku.php/strumenti/qmoveplus/mim1AD2F02 | |||
Language: | English | |||
Document release | Hardware release | Description | Note | Date |
01 | 02 | New manual | 17/12/2014 | |
02 | 02 | Improved description of the analog input connector table and fixed the hardware release of the card | 18/06/2015 | |
03 | 02 | Fixed the SW3 setting description and examplex | 01/02/2016 |
1. Description
The 1AD2F card of Qmove+ series.
1.1 Equipment
8 digital inputs | |
2 multistandard analog inputs 16bit | |
8 digital outputs |
2. Connections
2.1 Digital inputs
2.1.1 8 digital inputs
CN11 | Terminal | Simbol | Description | Address | |
---|---|---|---|---|---|
9 | 0V | Digital inputs common | |||
8 | I17 | Input I17 | 3.INP01 | ||
7 | I18 | Input I18 | 3.INP02 | ||
6 | I19 | Input I19 | 3.INP03 | ||
5 | I20 | Input I20 | 3.INP04 | ||
4 | I21 | Input I21 | 3.INP05 | ||
3 | I22 | Input I22 | 3.INP06 | ||
2 | I23 | Input I23 | 3.INP07 | ||
1 | I24 | Input I24 | 3.INP08 |
2.2 Analog inputs
2.2.1 2 multistandard analog inputs
Connector
CN13 | Terminal | Simbol | Description | Address | ||
---|---|---|---|---|---|---|
Potentiometric / 0-10V / 0-20mA | Termocouple | PT100 | ||||
1 | GAI | Analog inputs common | - | - | ||
2 | VREF | Reference volatege 1) | - | - | ||
3 | AI1_A | Analog input 1 | - | A 2) | 3.AI01 | |
4 | AI1_B | - | TC 1 - | B | ||
5 | AI1_C | - | TC 1 + | C | ||
6 | AI2_A | Analog input 2 | - | A 3) | 3.AI02 | |
7 | AI2_B | - | TC 2 - | B | ||
8 | AI2_C | - | TC 2 + | C |
Analog inputs setting
Num. Dip | Analog input 1 | Analog input 2 | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
PT100 | Termocouple | Pot. | 0-10V | 0-20mA | PT100 | Termocouple | Pot. | 0-10V | 0-20mA | ||
SW4 | 1 | ON | X | OFF | OFF | OFF | X | X | X | X | X |
2 | OFF | X | ON | ON | ON | X1) | X | X | X | X | |
3 | X | X | X | X | X | ON | X | OFF | OFF | OFF | |
4 | X2) | X | X | X | X | OFF | X | ON | ON | ON | |
5 | ON | ON | OFF | OFF | OFF | X | X | X | X | X | |
6 | OFF | OFF | ON | ON | ON | X | X | X | X | X | |
7 | OFF | ON | X | X | X | X | X | X | X | X | |
8 | X | X | X | X | X | OFF | ON | X | X | X | |
SW3 | 1 | X | X | X | X | X | X | X | OFF | OFF | ON |
2 | X | X | X | X | X | X | X | OFF | ON | OFF | |
3 | X | X | OFF | OFF | ON | X | X | X | X | X | |
4 | X | X | OFF | ON | OFF | X | X | X | X | X |
X = setting not significant
Pot. = potentiometric type input
2.3 Digital outputs
2.3.1 8 protected digital outputs
C12 | Terminal | Simbol | Description | Address |
---|---|---|---|---|
1 | V+ | Output power input (12÷28V dc) | ||
2 | O17 | Digital output 17 | 3.OUT01 | |
3 | O18 | Digital output 18 | 3.OUT02 | |
4 | O19 | Digital output 19 | 3.OUT03 | |
5 | O20 | Digital output 20 | 3.OUT04 | |
6 | O21 | Digital output 21 | 3.OUT05 | |
7 | O22 | Digital output 22 | 3.OUT06 | |
8 | O23 | Digital output 23 | 3.OUT07 | |
9 | O24 | Digital output 24 | 3.OUT08 | |
10 | V- | Output power input (0V dc) |
3. Connection examples
3.1 Digital inputs
3.2 Potentiometric analog input 1 and voltmetric analog input 2
3.3 PT100 analog input 1 per and amperometric inputs 2
3.4 PT100 analog input 1 and termocouple analog input 2
3.5 Protected digital outputs
4. Electrical features
The following are the electrical hardware features.
The maximum and minimum frequency values and actual acquisition times, can still depend on any additional software filters, see the system variable “QMOVE:sys004”.
4.1 Digital inputs
Type of polarisation | PNP |
Min. acquisition time (hardware) | 3ms |
Isolation | 1000Vrms |
Rated operating voltage | 24Vdc |
Voltage of logic state 0 | 0-2 V |
Voltage of logic state 1 | 10.5 - 26.5 V |
Internal voltage drop | 5V |
Input resistance (Ri) | 2700Ω |
Sink current | 2mA ÷ 8mA1) |
1)
CAUTION: If the device connected to the inputs needs a higher minimum current, inputs may not work properly.
4.2 Analog inputs
4.2.1 Conversion times
The electrical features depend on the type of input, configurable via DIP switch.
The conversion times from analog to digital depend on the configuration according to the table:
Analog Input Configuration | Conversion time per channel |
|
---|---|---|
Input 1 | Input 2 | |
DC1) | - | 4.6 ms |
- | DC2) | 4.6 ms |
DC3) | DC4) | 9.3 ms |
DC5) | TC | 9.3 ms |
DC6) | PT100 | 79.1 ms |
TC | - | 9.3 ms |
- | TC | 9.3 ms |
TC | DC7) | 9.3 ms |
TC | TC | 9.3 ms |
TC | PT100 | 83.8 ms |
PT100 | - | 74.5 ms |
- | PT100 | 74.5 ms |
PT100 | DC8) | 79.1 ms |
PT100 | TC | 79.1 ms |
PT100 | PT100 | 79.1 ms |
4.2.2 Amperometric analog inputs in 0-20mA configuration
Connection type | Amperometric (0-20 mA) |
Resolution | 12bit/16bit1) |
Input resistance | 125Ω |
Value of damage | 25 mA |
Max. Linearity error | + 0,1% Vfs |
Max. Offset error | + 0,1% Vfs |
S.n. | 71 dB |
Conversion time | It depends on the configuration of the analog input. See section Conversion times if present 2) |
Isolation | 1000 Vrms |
1)
It depends on the Hardware versions
2)
The sampling time of the device must be equal or higher than the conversion time
4.2.3 Potentiometric analog input configuration
Connection type | Potentiometric 1KΩ÷20KΩ |
Resolution | 12bit/16bit1) |
Reference voltage output | 2,5Vdc |
Max output current from reference | 10mA |
Input resistance | 10MΩ |
Max. Linearity error | + 0,1% Vfs |
Max. Offset error | + 0,1% Vfs |
S.n. | 71 dB |
Conversion time | It depends on the configuration of the analog input. See section Conversion times if present 2) |
Isolation | 1000 Vrms |
1)
It depend on the Hardware versions
2)
The sampling time of the device must be equal or higher than the conversion time
4.2.4 Ingresso analogico in configurazione volmetrica
Tipo di collegamento | Voltmetrico 0÷10V |
Risoluzione | 12bit/16bit1) |
Resistenza d'ingresso (Rin) | 40KΩ |
Valore di danneggiamento | 20V |
Max. errore di linearità | + 0,1% Vfs |
Max. errore di offset | + 0,1% Vfs |
S.n. | 71 dB |
Tempo di conversione | Dipende dalla configurazione dell'ingresso analogico. Vedi paragrafo Tempi di conversione se presente 2) |
Isolamento | 1000 Vrms |
1)
Dipende dalle Versioni hardware
2)
Il tempo di campionamento del device deve essere uguale o superiore al tempo di conversione
4.2.5 Ingresso analogico in configurazione PT100
Tipo di sensore collegabile | PT100 3 fili 1) |
Tipo di misura | Resistenza 2) |
Risoluzione | 15 bit (32767 corrisponde a 250.00 O) |
Resistenza d'ingresso (Rin) | 15 MO |
Corrente di misura | 1 mA |
Valore di danneggiamento | 10V |
Accuratezza misura resistenza | ± 0,04% |
Tempo di conversione | Dipende dalla configurazione dell'ingresso analogico. Vedi paragrafo Tempi di conversione se presente 3) |
Isolamento | 1000 Vrms |
4.2.6 Ingresso analogico in configurazione Termocoppia
Tipo di sensore collegabile | Termocoppia tipo J,K,R,S,B,N,T,E 1) |
Tipo di misura | Tensione differenziale |
Risoluzione | 16 bit |
Range di misura | ±156.25 mV |
Misura temperatura per compensazione giunto freddo | Integrata |
Resistenza d'ingresso (Rin) | 15 MO |
Valore di danneggiamento | 30V |
Accuratezza misura | ± 0,2% (esclusa compensazione giunto freddo ) |
Tempo di conversione | Dipende dalla configurazione dell'ingresso analogico. Vedi paragrafo Tempi di conversione se presente 2) |
Isolamento | 1000 Vrms |
4.2.7 Uscite digitali protette
Tipo | Sourcing (PNP) |
Max. tensione di funzionamento | 28V |
Caduta di tensione interna max. | 600mV |
Corrente massima | 500mA |
Tempo di massimo commutazione da ON a OFF | 270µs |
Tempo di massimo commutazione da OFF a ON | 250µs |